English (GB)
39
00518
Pump3Current
0.1 A
Motor current.
00519
Pump3LatestCurrent
0.1 A
Latest motor current.
00520
Pump3Voltage
0.1 V
Voltage.
00521
Pump3Insulation
10 k
Ω
Motor insulation resistance.
00522
Pump3WaterInOil
0.1 %
Motor water-in-oil measurement.
00523
Pump3Alarms1
Bits
00524
Pump3Alarms2
Bits
00525
Pump3Alarms3
Bits
00526
Pump3Warnings1
Bits
00527
Pump3Warnings2
Bits
00528
Pump3Warnings3
Bits
00529
Pump3MotorTemperature1
1 °C
Motor temperature 1.
00530
Pump3MotorTemperature2
1 °C
Motor temperature 2.
00531
Pump3PowerHI
1 W
Power consumption.
00532
Pump3PowerLO
00533
Pump3EnergyHI
0.1 kWh
Energy consumption.
00534
Pump3EnergyLO
00535
Pump3CosPhi
0.01
Motor cos
φ
.
00536
Pump3Frequency
0.1 Hz
Motor-applied frequency.
00537
Pump3VFDmode
enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00538
Pump3Torque
0.1 Nm
Motor torque.
00539
Pump3Asym
0.1 %
Line current asymmetry.
00540
Pump3Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump3Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00541
Pump3Alarms4
Bits
00542
Pump3Warnings4
Bits
00543
Pump3AntiBlockingCounter
Bits
Number of anti blockings in the pump
00544
Pump3AISetpointSelect
enum
Analog input used as setpoint for pump 3:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00545
Pump3SetpointType
enum
Setpoint type for pump 3:
0 = Fixed value
1 = Analog input
00546
Pump3FeedbackSensorType
enum
Feedback sensor type for pump 3:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00547
Pump3ControlMode
enum
Control mode for pump 3:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00548
Pump3ActualSetpoint
1 %
Actual setpoint for pump 3
00549
Pump3FixedFrequency
0.01 Hz
Fixed frequency for pump 3
Address
Register name
Scale
Description
Pumpland.ru
Summary of Contents for CIM 200