11.13 Alarms and warnings
These registers reflect the actual alarm/warning conditions of the
pit or the pump. Alarms/warnings which have acknowledgement
type "Auto-ack", will be cleared automatically when normal
conditions are restored. Alarms/warnings which have
acknowledgement type "Manual-ack", require a
PitControl.ResetAlarm command to be cleared.
Note
Warnings use the same bit interpretation as alarms.
Description
Data item
Code
Event source
Pit alarms 1 (register 00210),
Pit warnings 1 (register 00213)
Overflow alarm
PitAlarms/Warnings1.0
192
System
High-level alarm
PitAlarms/Warnings1.1
191
System
Alarm level alarm
PitAlarms/Warnings1.2
190
System
Dry-running alarm
PitAlarms/Warnings1.3
57
System
Mains supply fault
PitAlarms/Warnings1.4
6
System
Level float switch sequence inconsistency PitAlarms/Warnings1.5
205
System
Inconsistency between float switches and sensor
PitAlarms/Warnings1.6
204
System
Signal fault, level/pressure sensor
PitAlarms/Warnings1.7
168
AI (level sensor)
Signal fault, flow sensor
PitAlarms/Warnings1.8
169
AI (flow sensor)
Signal fault, power meter sensor
PitAlarms/Warnings1.9
186
AI (power sensor)
Fault, mixer contactor feedback
PitAlarms/Warnings1.10
221
DI (mixer contactor)
Communication fault, I/O module
PitAlarms/Warnings1.11
226
IO 351B
CIM fault (Communication Interface Module)
PitAlarms/Warnings1.12
159
Add-on CIM module
SIM card fault
PitAlarms/Warnings1.13
160
Add-on CIM module
Communication fault, main system (SCADA)
PitAlarms/Warnings1.14
15
System
Power-on notice
PitAlarms/Warnings1.15
247
System
Pit alarms 2 (register 00211),
Pit warnings 2 (register 00214)
Fault, battery/UPS
PitAlarms/Warnings2.0
248
Battery/UPS
Hardware fault, type 1
PitAlarms/Warnings2.1
72
CU 36X/IO 351B
Ethernet: No IP address from DHCP server
PitAlarms/Warnings2.2
231
System
Ethernet: Auto-disabled due to misuse
PitAlarms/Warnings2.3
232
System
Time for service, mixer
PitAlarms/Warnings2.4
222
Mixer
Maximum number of mixer starts per hour exceeded
PitAlarms/Warnings2.5
223
System
User-defined relay activated
PitAlarms/Warnings2.6
246
CU 36X
External fault signal
PitAlarms/Warnings2.8
3
System
Combi alarm No 1
PitAlarms/Warnings2.9
227
System
Combi alarm No 2
PitAlarms/Warnings2.10
227
System
Combi alarm No 3
PitAlarms/Warnings2.11
227
System
Combi alarm No 4
PitAlarms/Warnings2.12
227
System
Signal fault, user-defined sensor 1
PitAlarms/Warnings2.13
188
User-defined sensor, analog input 1
Signal fault, user-defined sensor 2
PitAlarms/Warnings2.14
188
User-defined sensor, analog input 2
Signal fault, user-defined sensor 3
PitAlarms/Warnings2.15
188
User-defined sensor, analog input 3
Pit alarms 3 (register 00212),
Pit warnings 3 (register 00215)
Discharge pressure sensor signal fault
PitAlarms/Warnings3.0
168
AI (Pressure sensor)
Water on floor alarm
PitAlarms/Warnings3.1
229
System
Gas detected alarm
PitAlarms/Warnings3.2
235
System
Uster event 1 alarm
PitAlarms/Warnings3.3
249
System
Uster event 2 alarm
PitAlarms/Warnings3.4
250
System
Uster event 3 alarm
PitAlarms/Warnings3.5
251
System
Uster event 4 alarm
PitAlarms/Warnings3.6
252
System
H2S signal sensor fault
PitAlarms/Warnings3.7
118
RESERVED
PitAlarms/Warnings3.8-15
Pit alarms 4 (register 00269),
Pit warnings 4 (register 00270)
Dosing pump over pressure alarm
PitAlarms/Warnings4.0
210
Dosing pump