English (GB)
49
9.19 Data log index register block
This is an index area for the configurable data log. The log data
index registers are read-only.
See section
11.3 Reading the configurable data log series
for
detailed information on how to read the configurable log series.
By default the configurable logs are not set up. This can only be
done with a PC Tool or via the CU 36X control panel. For further
information, see installation and operating instructions for
Dedicated Controls.
… indicates variable register address.
Address
Register name
Scale
Description
07001
NoOfLogSeries
Unscaled
Number of available log series [0; 64].
07002
LogSeries1ItemNo
Unscaled
Log series 1 item number.
See section
11.3 Reading the configurable data log series
07003
LogSeries1RegAddr
Unscaled
Register start address of log series 1.
07004
LogSeries1SamplingTime
1 second
Time period between samples in log series 1.
07005
LogSeries1NoOfSamples
Unscaled
Number of samples in log series 1, N
1
.
07006
LogSeries2ItemNo
Unscaled
Log series 2 item number.
See section
11.3 Reading the configurable data log series
07007
LogSeries2RegAddr
Unscaled
Register start address of log series 2.
07008
LogSeries2SamplingTime
1 second
Time period between samples in log series 2.
07009
LogSeries2NoOfSamples
Unscaled
Number of samples in log series 2, N
2
.
…
LogSeries#ItemNo
Unscaled
Log series # item number.
See section
11.3 Reading the configurable data log series
…
LogSeries#RegAddr
Unscaled
Register start address of log series #.
…
LogSeries#SamplingTime
1 second
Time period between samples in log series #.
…
LogSeries#NoOfSamples
Unscaled
Number of samples in log series #, N
#
.
07254
LogSeriesLItemNo
Unscaled
Log series "L" item number (last series).
See section
11.3 Reading the configurable data log series
07255
LogSeriesLRegAddr
Unscaled
Register start address of log series "L".
07256
LogSeriesLSamplingTime
1 second
Time period between samples in log series "L".
07257
LogSeriesLNoOfSamples
Unscaled
Number of samples in log series "L", N
L
.
07258
LogSeriesEndMark
Unscaled
End mark to end the index. Is always 0.