English (GB)
26
00205
PitPumpsDisabled
Bit 0: Pump1Disabled
Bool
Enabled/disabled state of pump 1.
0 = Enabled
1 = Disabled.
PitPumpsDisabled
Bit 1: Pump2Disabled
Bool
Enabled/disabled state of pump 2.
0 = Enabled
1 = Disabled.
PitPumpsDisabled
Bit 2: Pump3Disabled
Bool
Enabled/disabled state of pump 3.
0 = Enabled
1 = Disabled.
PitPumpsDisabled
Bit 3: Pump4Disabled
Bool
Enabled/disabled state of pump 4.
0 = Enabled
1 = Disabled.
PitPumpsDisabled
Bit 4: Pump5Disabled
Bool
Enabled/disabled state of pump 5.
0 = Enabled
1 = Disabled.
PitPumpsDisabled
Bit 5: Pump6Disabled
Bool
Enabled/disabled state of pump 6.
0 = Enabled
1 = Disabled.
PitPumpsDisabled
Bit 6: MixerDisabled
Bool
Enabled/disabled state of mixer.
0 = Enabled
1 = Disabled.
00206
PitPumpsRunning
Bit 0: Pump1Running
Bool
Running state of pump 1.
0 = Not running
1 = Running.
PitPumpsRunning
Bit 1: Pump2Running
Bool
Running state of pump 2.
0 = Not running
1 = Running.
PitPumpsRunning
Bit 2: Pump3Running
Bool
Running state of pump 3.
0 = Not running
1 = Running.
PitPumpsRunning
Bit 3: Pump4Running
Bool
Running state of pump 4.
0 = Not running
1 = Running.
PitPumpsRunning
Bit 4: Pump5Running
Bool
Running state of pump 5.
0 = Not running
1 = Running.
PitPumpsRunning
Bit 5: Pump6Running
Bool
Running state of pump 6.
0 = Not running
1 = Running.
PitPumpsRunning
Bit 6: MixerRunning
Bool
Running state of mixer.
0 = Not running
1 = Running.
00207
PitPumpsMonitoringFault
Bit 0: Pump1MonitoringFault
Bool
Fault state of pump 1 monitoring devices, e.g. IO 111.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
PitPumpsMonitoringFault
Bit 1: Pump2MonitoringFault
Bool
Fault state of pump 2 monitoring devices, e.g. IO 111.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
PitPumpsMonitoringFault
Bit 2: Pump3MonitoringFault
Bool
Fault state of pump 3 monitoring devices, e.g. IO 111.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
PitPumpsMonitoringFault
Bit 3: Pump4MonitoringFault
Bool
Fault state of pump 4 monitoring devices, e.g. IO 111.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
PitPumpsMonitoringFault
Bit 4: Pump5MonitoringFault
Bool
Fault state of pump 5 monitoring devices, e.g. IO 111.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
PitPumpsMonitoringFault
Bit 5: Pump6MonitoringFault
Bool
Fault state of pump 6 monitoring devices, e.g. IO 111.
0 = No fault
1 = Fault in auxiliary equipment or sensors.
PitPumpsMonitoringFault
Bit 6: MixerMonitoringFault
Bool
Monitoring fault on mixer
0 = No fault
1 = Fault in auxiliary equipment or sensors.
Address
Register name
Scale
Description