English (GB)
65
Pump alarms 1 (registers 00423 (pump 1), 00473 (pump 2), 00523 (pump 3), 00573 (pump 4), 00623 (pump 5), 00673 (pump 6))
Pump warnings 1 (registers 00426 (pump 1), 00476 (pump 2), 00526 (pump 3), 00576 (pump 4), 00626 (pump 5), 00676 (pump 6))
Motor temperature alarm, PTC1
PumpAlarms/warnings1.0
69
IO 111, pump No [1; 6]
Motor temperature alarm, PTC2
PumpAlarms/warnings1.1
70
IO 351B/MP 204/CUE, pump No [1; 6]
Motor stator temperature high (T1, Pt1000/Pt100)
PumpAlarms/warnings1.2
64
IO 111/CUE, pump No [1; 6]
Motor stator temperature high (T2, Pt1000/Pt100)
PumpAlarms/warnings1.3
71
MP 204, pump No [1; 6]
Motor support bearing temperature high (Pt100)
PumpAlarms/warnings1.4
145
IO 111, pump No [1; 6]
Motor main bearing temperature high (Pt100)
PumpAlarms/Warnings1.5
146
IO 111, pump No [1; 6]
Motor insulation resistance low
PumpAlarms/Warnings1.6
20
IO 111/MP 204, pump No [1; 6]
Motor low voltage (no voltage)
PumpAlarms/Warnings1.7
40
MP 204/CUE, pump No [1; 6]
Motor high voltage
PumpAlarms/Warnings1.8
32
MP 204/CUE, pump No [1; 6]
Motor phase sequence reversal
PumpAlarms/Warnings1.9
9
MP 204, pump No [1; 6]
Motor overload (maximum current)
PumpAlarms/Warnings1.10
48
AI/MP 204/CUE, pump No [1; 6]
Motor underload (minimum current)
PumpAlarms/Warnings1.11
56
AI/MP 204, pump No [1; 6]
Motor protector test trip
PumpAlarms/Warnings1.12
27
DI/MP 204, pump No [1; 6]
Motor missing phase
PumpAlarms/Warnings1.13
2
MP 204/CUE, pump No [1; 6]
Motor current asymmetry
PumpAlarms/Warnings1.14
111
MP 204, pump No [1; 6]
Load continues even if the motor relay is off
PumpAlarms/Warnings1.15
26
MP 204, pump No [1; 6]
Pump alarms 2 (registers 00424 (pump 1), 00474 (pump 2), 00524 (pump 3), 00574 (pump 4), 00624 (pump 5), 00674 (pump 6))
Pump warnings 2 (registers 00427 (pump 1), 00477 (pump 2), 00527 (pump 3), 00577 (pump 4), 00627 (pump 5), 00677 (pump 6))
Motor protector commanded (test) trip
PumpAlarms/Warnings2.0
18
MP 204, pump No [1; 6]
Common phase error
PumpAlarms/Warnings2.1
241
DI/CUE, pump No [1; 6]
Motor moisture switch
PumpAlarms/Warnings2.2
22
IO 111, pump No [1; 6]
Motor/pump vibration high
PumpAlarms/Warnings2.3
24
IO 111, pump No [1; 6]
Motor water-in-oil content too high (water in oil)
PumpAlarms/Warnings2.4
11
AI/IO 111, pump No [1; 6]
Motor fault in mains supply
PumpAlarms/Warnings2.5
6
DI, pump No [1; 6]
Motor contactor feedback fault
PumpAlarms/Warnings2.6
220
DI, pump No [1; 6]
Motor max. starts per hour limit exceeded
PumpAlarms/Warnings2.7
21
System, pump No [1; 6]
Motor operating time service limit exceeded
PumpAlarms/Warnings2.8
12
Pump No [1; 6]
Too many pump auto-restarts (per 24 h)
PumpAlarms/Warnings2.9
4
MP 204, pump No [1; 6]
Pump low flow
PumpAlarms/Warnings2.10
58
Pump No [1; 6]
Pump max. continuous runtime limit exceeded
PumpAlarms/Warnings2.11
245
System, pump No [1; 6]
Motor cos
φ
too high
PumpAlarms/Warnings2.12
112
MP 204, pump No [1; 6]
Motor cos
φ
too low
PumpAlarms/Warnings2.13
113
MP 204, pump No [1; 6]
Pump alarms 3 (registers 00425 (pump 1), 00475 (pump 2), 00525 (pump 3), 00575 (pump 4), 00625 (pump 5), 00675 (pump 6))
Pump warnings 3 (registers 00428 (pump 1), 00478 (pump 2), 00528 (pump 3), 00578 (pump 4), 00628 (pump 5), 00678 (pump 6))
Pump malfunction due to auxiliary component fault
PumpAlarms/Warnings3.0
224
Pump No [1; 6]
Communication fault, pump module
PumpAlarms/Warnings3.1
225
IO 111, pump No [1; 6]
On/Off/Auto switch fault
PumpAlarms/Warnings3.2
244
DI, pump No [1; 6]
Signal fault, Pt100 sensor
PumpAlarms/Warnings3.3
175
IO 111/MP 204/CUE, pump No [1; 6]
Signal fault, PTC sensor
PumpAlarms/Warnings3.4
181
IO 111, pump No [1; 6]
Signal fault, water-in-oil (WIO)
PumpAlarms/Warnings3.5
170
AI, pump No [1; 6]
Signal fault, bearing temperature sensor (Pt100),
general or top bearing
PumpAlarms/Warnings3.6
179
IO 111, pump No [1; 6]
Signal fault, bearing temperature sensor (Pt100),
middle bearing
PumpAlarms/Warnings3.7
180
IO 111, pump No [1; 6]
Communication fault, pump
PumpAlarms/Warnings3.8
10
IO 111, pump No [1; 6]
Setup conflict
PumpAlarms/Warnings3.9
25
IO 111, pump No [1; 6]
General hardware fault
PumpAlarms/Warnings3.10
72
IO 111/MP 204, pump No [1; 6]
Signal fault, motor current sensor
PumpAlarms/Warnings3.11
88
AI, pump No [1; 6]
Inrush fault
PumpAlarms/Warnings3.12
155
CUE, pump No [1; 6]
Signal fault, sensor 2
PumpAlarms/Warnings3.13
93
CUE, pump No [1; 6]
Motor bearing temperature high (Pt100) in drive end
(DE)
PumpAlarms/Warnings3.14
148
CUE, pump No [1; 6]
Motor bearing temperature high (Pt100) in non-drive
end (NDE)
PumpAlarms/Warnings3.15
149
CUE, pump No [1; 6]
Description
Data item
Code
Event source
Pumpland.ru
Summary of Contents for CIM 200
Page 92: ...92 Pumpland ru...