9. Modbus register overview
9.1 Register block overview
The Modbus RTU registers are grouped in the following register
blocks:
All addresses contain registers. Some are bit-interpreted while
others are 16-bit values, or high/low order parts of 32-bit values.
A data value of 65535 (0xFFFF) indicates "not available" when
reading registers. The value of 65535 (0xFFFF) does not imply a
"disable" when writing values.
Each register block will be specified in more detail in the following
sections.
Start address
Register block
Permissions
Description
00001
CIM configuration
R/W
Configuration of the CIM module.
00021
CIM status
R
Status registers for the CIM module.
00101
Pit control and configuration R/W
Registers for control and configuration of wastewater pit.
00201
Pit status
R
Registers for status from wastewater pit.
00301
Pit data
R
Registers for measured values from wastewater pit.
00401
Pump 1
R
Registers containing pump 1 data and status.
00451
Pump 2
R
Registers containing pump 2 data and status.
00501
Pump 3
R
Registers containing pump 3 data and status.
00551
Pump 4
R
Registers containing pump 4 data and status.
00601
Pump 5
R
Registers containing pump 5 data and status.
00651
Pump 6
R
Registers containing pump 6 data and status.
00701
Alarm simulation
R/W
Registers for simulation of alarms and warnings.
00751
User
R/W
Registers where the user can freely store data.
00801
Name string
R
For reading the name string from the CU 361.
02001
Hour log
R
Registers containing 72-hour logs.
06001
Event log
R
Registers containing the latest 50 event log entries.
07001
Data log index
R
Index for the configurable data log series.
07301
Data log series
R
Configurable data log series.