00668
Pump6Current
0.1 A
Motor current.
00669
Pump6LatestCurrent
0.1 A
Latest motor current.
00670
Pump6Voltage
0.1 V
Voltage.
00671
Pump6Insulation
10 k
Ω
Motor insulation resistance.
00672
Pump6WaterInOil
0.1 %
Motor water-in-oil measurement.
00673
Pump6Alarms1
Bits
See section
00674
Pump6Alarms2
Bits
See section
00675
Pump6Alarms3
Bits
See section
00676
Pump6Warnings1
Bits
See section
00677
Pump6Warnings2
Bits
See section
00678
Pump6Warnings3
Bits
See section
00679
Pump6MotorTemperature1
1 °C
Motor temperature 1.
00680
Pump6MotorTemperature2
1 °C
Motor temperature 2.
00681
Pump6PowerHI
1 W
Power consumption.
00682
Pump6PowerLO
00683
Pump6EnergyHI
0.1 kWh
Energy consumption.
00684
Pump6EnergyLO
00685
Pump6CosPhi
0.01
Motor cos
φ
.
00686
Pump6Frequency
0.1 Hz
Motor-applied frequency.
00687
Pump6VFDmode
enum
Mode of variable-frequency drive.
0 = VFD not controlled
1 = -
2 = Stopped
3 = Reverse start
4 = Start flushing
5 = Normal
6 = Run flushing
7 = Stop flushing
8 = Specific-energy test.
00688
Pump6Torque
0.1 Nm
Motor torque.
00689
Pump6Asym
0.1 %
Line current asymmetry.
00690
Pump6Sensors.WIO
Bit 0: WaterInOilSensor
Bool
Presence of water-in-oil (WIO) sensor.
0 = Not present
1 = Present.
Pump6Sensors.Current
Bit 1: MotorCurrentSensor
Bool
Presence of current sensor.
0 = Not present
1 = Present.
00691
Pump6Alarms4
Bits
See section
00692
Pump6Warnings4
Bits
See section
00693
Pump6AntiBlockingCounter
Bits
Number of anti blockings in the pump
00694
Pump6AISetpointSelect
enum
Analog input used as setpoint for pump 6:
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00695
Pump6SetpointType
enum
Setpoint type for pump 6:
0 = Fixed value
1 = Analog input
00696
Pump6FeedbackSensorType
enum
Feedback sensor type for pump 6:
4 = Flow rate
5 = Level, pressure
6 = Level, ultrasound
13 = User defined sensor 1
14 = User defined sensor 2
15 = User defined sensor 3
00697
Pump6ControlMode
enum
Control mode for pump 6:
0 = Fixed frequency
1 = Linear control
2 = Minimum control
3 = PID control
00698
Pump6ActualSetpoint
1 %
Actual setpoint for pump 6
00699
Pump6FixedFrequency
0.01 Hz
Fixed frequency for pump 6