English (GB)
47
9.17 Hour log register block
Generally the Modbus master application can select the relevant
log series and the relevant number of hours back in time.
Typically several communication sessions (request telegrams)
are needed to read the data.
The communication interface ensures that logged data is
protected against internal update during the time it is accessed
from Modbus, so that the Hour log constitutes a time-consistent
block (data coherency). Every time the real-time clock increments
by one hour, all the logged data in the hour log is shifted one hour
back in time (and the oldest data set is cleared). The exact time
where this happens will be delayed a few seconds relative to the
hour incrementation, so to be sure to read hour log data that has
been correctly updated, we recommend reading data at least 30
seconds after the hour incrementation.
Address
Register name
Scale
Description
02001-02072
PitOverflowTimeHourLog1…72
1 minute
Pit, incremental overflow time, hour log 1…72.
02073-02144
PitOverflowCntHourLog1…72
Unscaled Pit, incremental number of overflows, hour log 1…72.
02145-02216
PitOverflowVolumeHourLog1…72
0.1 m
3
Pit, incremental overflow volume, hour log 1…72.
02217-02288
PitSpecificEnergyHourLog1…72
1 Wh/m
3
Pit, specific energy, hour log 1…72.
02289-02360
PitVolumeHourLog1…72
0.1 m
3
Pit, incremental pumped volume, hour log 1…72.
02361-02432
PitEnergyHourLog1…72
0.1 kWh
Pit, incremental energy consumption, hour log 1…72.
02433-02504
Pit2PumpsOprTimeHourLog1…72
1 minute
Pit, incremental operating time (two pumps operating simultaneously),
hour log 1…72.
02505-02576
Pit3PumpsOprTimeHourLog1…72
1 minute
Pit, incremental operating time (three pumps operating
simultaneously), hour log 1…72.
02577-02648
Pit4PumpsOprTimeHourLog1…72
1 minute
Pit, incremental operating time (four pumps operating simultaneously),
hour log 1…72.
02649-02720
Pit5PumpsOprTimeHourLog1…72
1 minute
Pit, incremental operating time (five pumps operating simultaneously),
hour log 1…72.
02721-02792
Pit6PumpsOprTimeHourLog1…72
1 minute
Pit, incremental operating time (six pumps operating simultaneously),
hour log 1…72.
02793-02864
Pump1OprTimeHourLog1…72
1 minute
Pump 1, incremental operating time, hour log 1…72.
02865-02936
Pump1StartCntHourLog1…72
Unscaled Pump 1, incremental number of starts, hour log 1…72.
02937-03008
Pump1AvgFlowHourLog1…72
0.1 litre/s Pump 1, average flow, hour log 1…72.
03009-03080
Pump1AvgCurrentHourLog1…72
0.1 A
Pump 1, average current, hour log 1…72.
03081-03152
Pump2OprTimeHourLog1…72
1 minute
Pump 2, incremental operating time, hour log 1…72.
03153-03224
Pump2StartCntHourLog1…72
Unscaled Pump 2, incremental number of starts, hour log 1…72.
03225-03296
Pump2AvgFlowHourLog1…72
0.1 litre/s Pump 2, average flow, hour log 1…72.
03297-03368
Pump2AvgCurrentHourLog1…72
0.1 A
Pump 2, average current, hour log 1…72.
03369-03440
Pump3OprTimeHourLog1…72
1 minute
Pump 3, incremental operating time, hour log 1…72.
03441-03512
Pump3StartCntHourLog1…72
Unscaled Pump 3, incremental number of starts, hour log 1…72.
03513-03584
Pump3AvgFlowHourLog1…72
0.1 litre/s Pump 3, average flow, hour log 1…72.
03585-03656
Pump3AvgCurrentHourLog…72
0.1 A
Pump 3, average current, hour log 1…72.
03657-03728
Pump4OprTimeHourLog1…72
1 minute
Pump 4, incremental operating time, hour log 1…72.
03729-03800
Pump4StartCntHourLog1…72
Unscaled Pump 4, incremental number of starts, hour log 1…72.
03801-03872
Pump4AvgFlowHourLog1…72
0.1 litre/s Pump 4, average flow, hour log 1…72.
03873-03944
Pump4AvgCurrentHourLog…72
0.1 A
Pump 4, average current, hour log 1…72.
03945-04016
Pump5OprTimeHourLog1…72
1 minute
Pump 5, incremental operating time, hour log 1…72.
04017-04088
Pump5StartCntHourLog1…72
Unscaled Pump 5, incremental number of starts, hour log 1…72.
04089-04160
Pump5AvgFlowHourLog1…72
0.1 litre/s Pump 5, average flow, hour log 1…72.
04161-04232
Pump5AvgCurrentHourLog…72
0.1 A
Pump 5, average current, hour log 1…72.
04233-04304
Pump6OprTimeHourLog1…72
1 minute
Pump 6, incremental operating time, hour log 1…72.
04305-04376
Pump6StartCntHourLog1…72
Unscaled Pump 6, incremental number of starts, hour log 1…72.
04377-04448
Pump6AvgFlowHourLog1…72
0.1 litre/s Pump 6, average flow, hour log 1…72.
04449-04521
Pump6AvgCurrentHourLog…72
0.1 A
Pump 6, average current, hour log 1…72.
Pumpland.ru
Summary of Contents for CIM 200