English (GB)
50
9.20 Data log series register block
Data area for the configurable data log series (max. 64 series).
The log data are read-only and have a fixed starting address, so
log series 1 always starts at register 07301.
See section
11.3 Reading the configurable data log series
for
detailed information on how to read the configurable log series.
… indicates variable register address.
Address
Register name
Scale
Description
07301
LogSeries1ItemNo
Unscaled
Log series 1 item number.
See section
11.3 Reading the configurable data log series
07302
LogSeries1SamplingTime
1 second
Time period between samples in log series 1, configurable
on the CU 36X control panel.
07303
LogSeries1NoOfSamples
Unscaled
Number of samples in log series 1, N
1
, configurable on the
CU 36X control panel.
07304
LogSeries1TimeStampHI
1 second
Log series 1 Unix time stamp. Subtracting "Sampling time"
gives the time stamp of sample No 2 in this series, etc.
07305
LogSeries1TimeStampLO
07306
LogSeries1Sample1
-
Value of log series 1 sample No 1.
…
LogSeries1SampleN1
-
Value of log series 1 sample No N
1
(last sample in series).
…
LogSeries2ItemNo
-
Log series 2 item number.
See section
11.3 Reading the configurable data log series
…
LogSeries2SamplingTime
-
Time period between samples in log series 2, configurable
on the CU 36X control panel.
…
LogSeries2TimeStampHI
-
Log series 2 Unix time stamp. Subtracting "Sampling time"
gives the time stamp of sample No 2 in this series, etc.
…
LogSeries2TimeStampLO
…
LogSeries2Sample1
-
Value of log series 2 sample No 1.
…
…
-
-
…
LogSeries2SampleN2
-
Value of log series 2 sample No N
2
(last sample in series).
…
LogSeries#ItemNo
-
Log series # item number.
See section
11.3 Reading the configurable data log series
…
LogSeries#SamplingTime
-
Time period between samples in log series #.
…
LogSeries#NoOfSamples
-
Number of samples in log series #, N
#
.
…
LogSeries#TimeStampHI
-
Log series # Unix time stamp. Subtracting "Sampling time"
gives the time stamp of sample No 2 in this series, etc.
…
LogSeries#TimeStampLO
…
LogSeries#Sample1
-
Value of log series # sample No 1.
…
…
-
-
…
LogSeries#SampleN#
-
Value of log series # sample No N
#
(last sample in series).
…
LogSeriesLItemNo
-
Log series "L" item number.
See section
11.3 Reading the configurable data log series
…
LogSeriesLSamplingTime
-
Time period between samples in log series "L".
…
LogSeriesLNoOfSamples
-
Number of samples in log series "L", N
L
.
…
LogSeriesLTimeStampHI
-
Log series "L" Unix time stamp. Subtracting "Sampling
time" gives the time stamp of sample No 2 in this series,
etc.
…
LogSeriesLTimeStampLO
…
LogSeriesLSample1
-
Value of log series "L" sample No 1.
…
…
-
-
…
LogSeriesLSampleN1
-
Value of log series "L" sample No N
L
(last sample in
series).