ECOLOGIC 30 | instructions for use, maintenance and installation |
June 2015
36
YE
S
YE
S
NO
NO
NO
service person
safety thermostat is
clogged
Is boiler temperature above
95 degrees?
1. Cool the boiler and press button STB again
2. If the error remains, check set boiler temperature
3. Check heat take-off from boiler
1. Replace STB
2. Check wiring between STB and electronics in accordance with scheme
excessive temperature
of smoke gases (above
250 degrees)
Is the exchanger clogged?
1. Check and clean the exchanger
2. In case of automatic cleaning, check operation of
cleaning mechanism
Are all turbulators in their
places?
Install or replace turbulators