AQUA ECOLOGIC | instructions for use, maintenance and installation |
September 2015
49
4. The doors are not closed
properly or the glass sealing is
worn out.
5. Inadequate wooden granules.
6.
Poor
supply
of
wooden
granules.
7. The combustion chamber is
empty.
8. The chimney is clogged.
9. Interference of failure of the
pressure switch.
10. The smoke vacuum motor is
defective.
5. Change the type of the wooden granules
and pick the type that is approved by the
manufacturer.
6. Check the dosage and settings.
7.Clean the combustion chamber as
instructed in the manual.
8. Clean the smoke channel.
9. Change the pressure switch.
10.
Check the motor and change if needed.
It worked for a
couple of minutes
but then it turned
off.
1. The ignition phase is not over.
2. Check if there is an electricity
interruption.
3. The smoke channel is clogged.
4. Interference of failure of the
pressure switch.
5. The spark plug is damaged.
1. Try igniting again.
2. See last instruction.
3. The smoke channel is clogged.
4.
Check or change the probe.
5.
Check or change the spark plug.
Wooden granules
are settling in the
combustion
chamber.
The glass on the
door is dirty and
the flame is weak.
1. Lack of air for combustion.
2. Wet or inadequate wooden
granules.
3. The smoke vacuum system
motor is defective.
1. Clean the combustion chamber and check
if all the openings are clear. Do the standard
cleaning of the combustion chamber and the
smoke channel. Check if air flow is clogged.
Check the gaskets on the door.
2. Change the type of the wooden granules.
3. Check the motor and change if needed.
The
smoke
vacuum motor is
defective.
1. The stove is not receiving the
electricity.
2. The motor is defective.
3. Motherboard is defective.
4. The control panel is defective.
1. Check the main power supply and
resistance to melting.
2. Check the motor and condenser; change
if needed.
3.
Change the electronic card.
4.
Change the control panel.
In automatic mode
the stove works at
maximum
1. The thermostat is programmed
to the maximum position.
1. Set the thermostat temperature again.
2. Change the probe position.
3.
Check the probe and change if needed.
Summary of Contents for Aqua ECOLOGIC
Page 32: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 32 Figure 12...
Page 41: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 41 service...
Page 42: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 42 service...
Page 43: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 43 service...
Page 44: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 44 service...
Page 45: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 45 service...
Page 52: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 52...