ECOLOGIC 30 | instructions for use, maintenance and installation |
June 2015
35
NO
NO
NO
NO
YE
S
YE
S
YE
S
NO
service person
fault of safety pressure
control
Clogged air intake?
1. Check air intake into space
2. Check entry point of air into boiler
3. Check dirtiness of burning container and space
beneath it
Are the tubes between
electronics and flow meter
in order?
1. If torn or damaged, replace
2. If clogged or squeezed, clean or reinstall correctly
Is there a failure in flow
meter?
Replace electronics
Does fan FAN1 (overpressure
fan) work?
1. Check voltage output from electronics
2. Check white round safety pressure control
3. Check STB
4. Check functioning of safety relay
5. Replace fan