
ECOLOGIC 30 | instructions for use, maintenance and installation |
June 2015
34
NO
NO
YE
S
YE
S
YE
S
NO
YE
S
service person
air flow through
burner
Clogged air intake?
1. Check air intake into space
2. Check entry point of air into boiler
3. Check dirtiness of burning container and space
beneath it
Does fan FAN1 (overpressure
fan) work?
1. Check voltage output from electronics
2. Check white round safety pressure control
3. Check STB
4. Check functioning of safety relay
5. Replace fan
Are the tubes between
electronics and flow meter in
order?
1. If torn or damaged, replace
2. If clogged or squeezed, clean or reinstall correctly
Is there a failure in flow meter?
Replace electronics
Summary of Contents for Aqua ECOLOGIC
Page 32: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 32 Figure 12...
Page 41: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 41 service...
Page 42: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 42 service...
Page 43: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 43 service...
Page 44: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 44 service...
Page 45: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 45 service...
Page 52: ...AQUA ECOLOGIC instructions for use maintenance and installation September 2015 52...