BCT_T Rev.00 05-2015
pag. 134
Pr4
Needle probe error 1.
Solutions:
-
the same as the cabinet probe error (“
Pr1
” code) but relative to the needle probe 1.
ain consequences if parameter P3 is set at 1:
-
if the error occurs during the “stand-by” status, temperature-controlled operating cycles will be
started by time-control
-
if the error occurs during temperature-controlled blast chilling, this will have duration of the time
set by parameter r1
-
if the error occurs during temperature-controlled deep freezing, this will have duration of the time
set by parameter r2
-
if the error occurs during needle probe heating, this operation will be interrupted.
-
the alarm output will be activated.
ain consequences if parameter P3 is set at 2 or at 3:
-
the device will not use needle probe 1.
Pr5
Needle probe error 2.
Solutions:
-
the same as the cabinet probe error (“
Pr1
” code) but relative to the needle probe 2.
Main consequences:
-
the device will not use needle probe 2.
Pr6
Needle probe error 3.
Solutions:
-
the same as the cabinet probe error (“
Pr1
” code) but relative to the needle probe 3.
Main consequences:
-
the device will not use needle probe 3.
rtc
Clock error.
Solutions:
-
set the real date and time again.
Main consequences:
-
the device does not memorise the date or time at which the HACCP alarm occurred or its
duration
-
the alarm output will be activated.
ErC
User interface-control module compatibility.
Solutions:
-
check that the user interface and the control module are compatible.
Main consequences:
-
the control module will continue to operate normally.
ErL
User interface-control module communication error.
Solutions:
-
check user interface-control module control module.
Main consequences:
-
the control module will continue to operate normally.