Operate as indicated to stop the cycle:
6.
Press and hold the START/STOP key 3 s.
The successive parameters establish the following values:
-
parameter r3 establishes the blast chilling end temperature
-
parameter r5 establishes the maximum blast chilling duration
-
parameter r7 establishes the work set-point during blast chilling.
If the temperature detected by the needle probe reaches the blast chilling end temperature within the maximum blast
chilling duration, it means that blast chilling has been completed successfully, the device will automatically pass to
storage and the buzzer will be activated for the period of time established with parameter AA.
Press and release a key to silence the buzzer.
During storage the device displays the temperature of the cabinet, the program name (if envisioned) and the time taken
to complete blast chilling successfully.
Parameter r10 establishes the work set-point during storage.
If the temperature detected by the needle probe does not reach the blast chilling end temperature within the maximum blast
chilling duration, blast chilling will not be completed successfully but will continue and the buzzer will be activated.
Press and release a key to restore normal display and to silence the buzzer.
When the temperature detected by the needle probe reaches the blast chilling end temperature, the device automatically
passes to storage in the same way as illustrated previously.
7.5.4
– TEMPERATURE – CONTROLLED HARD BLAST CHILLING AND STORAGE
Temperature-controlled hard blast chilling and storage
The temperature-controlled hard blast chilling and storage cycle is divided into the following three phases:
-
blast chilling hard phase
-
blast chilling
-
storage.