BCT_T Rev.00 05-2015
pag. 107
4.1
Press and release the MENU key and then press and release the
key or the
key to select the deep freezing
duration and the work set-point during deep freezing.
4.2
Press and release the
key or the
key to modify these values and then the ESCAPE key to memorise them;
these values can also be memorised through parameters r2 and r8.
5.
Press and release the START/STOP key (1): the cycle will be started.
During blast chilling the device displays the residual deep freezing time, the temperature of the cabinet, the name of the
program (if envisioned) and the time passed from the start of deep freezing.
Operate as indicated to stop the cycle:
6.
Press and hold the START/STOP key 3 s.
The successive parameters establish the following values:
-
parameter r2 establishes deep freezing duration
-
parameter r8 establishes the work set-point during deep freezing.
On expiry of the deep freezing duration, the device automatically passes to storage mode and the buzzer is activated for
the time period established with parameter AA.
Press and release a key to silence the buzzer.
During deep freezing the device displays the temperature of the cabinet, the program name (if envisioned) and the
duration of deep freezing.
Parameter r11 establishes the work set-point during storage.