Since the up and down phases of the load have different work conditions, they use two individually settable
power setpoints (target values).
Therefore, if the motor is sized to devote 50% of its nominal power to supporting the load and 50% to
acceleration:
when the load rises, since the force of gravity helps in the deceleration phase, a value approaching
nominal value of the motor (default = 90%) can be used as the maximum limit
when the load descends, because additional braking power must be supplied during deceleration, the
power limit must be set at 50%
Note: If you use –ELS (electric shaft) configuration
):
The thresholds are set in % only on the drive defined as “virtual master” …–ELS-VM. The “virtual master”
receives the load %s of each shaft from the slaves.
The action if the threshold is exceeded must be specified only on drive…–ELS-VM.
Function activation state will be shown on the monitor on drive …-ELS-VM