4.2 COMMISSIONING PROCEDURE
4.2.1
General information
The following chapter describes a commissioning procedure for the application.
Preliminary commissioning operations for ADV200 drives are described in chapter 7 of the manual “ADV200
Rapid installation guide – Specifications and connections.”
To install application you need:
•
PC
•
GF_Express configuration software (
≥ 1.9.2) and Catalog (≥ 2.20.0).
4.2.2
Initial operations
• Check all connections. Pay particular attention to shieldings in order to minimize noise, especially with
regard to the encoder.
• To connect to the drive, you need a PC, GF_express configuration software with catalog version equal to
or later than 1.9.4, and the RS485 - PCI COM drive connection kit.
• Launch the Gf_eXpress software click DRIVES, then select INVERTER and ADV200 HC on the pull-
down menu. The next screen shows the drives connected to the PC: if no drives are detected, open the
Manual screen and check the connection settings.
• Click PARAMETERS.
• Load the default parameters and run the "Load default drive values" command on the Gf_eXpress
Parameters menu.
• First run a “Save parameter into target” command and then a “Drive reset” command.
• Run the guided startup operation, which proposes a procedure for rapid commissioning of the drive with a
minimum number of settings. For customized/advanced commissioning, you have to use the individual
parameters for the functions required. To do this, see the procedure described in chapter 7.1.1 Guided
startup of the manual “Rapid installation guide (ADV200 QS).”
Use “stand-still” mode to self-calibrate the motor.
4.2.3
Drive parameters managed by the application
The Hoist application automatically configures a few standard parameters of the drive.
Therefore, it is essential that application parameters be loaded ONLY after the motor
commissioning procedure has finished.
In case of error, you should reload the drive default parameters by running the “Load default
drive values” command on the Parameters menu of the GF_express configurator.
.
•
Load the application default values by running the "H&C SERVICE \App Load default" command
(IPA 11144).
Attention: when setting a default load for drive parameters, you have to reload the application
parameters (see COMMISSIONING PROCEDURE)
4.2.3.1
List of ADV parameters changed when loading application default parameters
MENU
PAR
Description
UM
Type
Default for application
22.14.01
556
Control mode select
*
ENUM
Speed
06.22
752
Ramp out Zero src
*
ENUM
One
11.01
1000
Set cmd remot
*
BOOL
Digital