NetworX Version 3 Installation Manual
212
Reporting with partition modifiers
Partition modifiers are used to identify partitions. Events with partition modifiers are sent using the
syntax:
• >aaaaaa eennn[/Rin] [eennn[/Rin] …].
See Table 30 for a detailed syntax description.
The settings and events in Table 31 are transmitted in the following message.
• > 987654 BA001/Ri1 BA003/Ri1 YT000 TA030/Ri3.
SMS Contact ID reporting
Each SMS message contains only one event. The information in the message is the same as a Contact
ID message sent over the PSTN with the digits coded using ASCII instead of DTMF.
The following syntax is used
• aaaa18qnnnggppp
Table 32.
Contact ID reporting syntax
Format key
Description
aaaa
Account number for the event that follows. Hexadecimal digits A - F are in upper case
18
Shows that this is a Contact ID message.
q
Contact ID qualifier. '1' = activation, '3' = restore.
nnn
Three-digit Contact ID event number (decimal).
gg
Two-digit group number (decimal). This contains the partition that generated the event, or zero
for a non-partition event
ppp
Three-digit point number (decimal). This contains the zone, user or module number for the event.
0
Contact ID checksum. This ‘0’ can be ignored.
Example
The following example shows Partition 3 account code E9D3 has a keypad tamper (Contact ID 137)
on zone 30 partition 3.
• E9D318113703030
Table 33.
Contact ID example
Part of Message
Format key
Description
E9D3
aaaaa
Account number E9D3
18
18
Shows that this is a Contact ID message.
Summary of Contents for NetworX V3
Page 1: ...NetworX Version 3 Alarm System Installation Manual 1070138 ...
Page 10: ...NetworX Version 3 Installation Manual 10 Section A Installing and programming a basic system ...
Page 50: ...NetworX Version 3 Installation Manual 50 Section B Programming the system ...
Page 257: ...NetworX Version 3 Installation Manual 257 Section C References ...