NetworX Version 3 Installation Manual
125
LOCATION 97 - PARTITION 4 ENTRY EXIT TIMERS (6 segments, numerical data)
Location 97 is used to enter the entry and exit times in seconds. There are 2 separate entry and exit
times. Valid entries are 10-255 seconds. If all the segments are “0”, the entry and exit times for
partition 1 will be used.
Segment 1
Entry time 1
Entry time that will be used when a delay 1 zone type
initiates an entry delay
Segment 2
Exit time 1
Exit time that will be used for all zones designated as delay 1
Segment 3
Entry time 2
Entry time that will be used when a delay 2 zone type
initiates an entry delay
Segment 4
Exit time 2
Exit time that will be used for all zones designated as delay 2
Segment 5
Reserved
Segment 6
Reserved
Programming zone configuration groups
Locations 110-169 are used to change the zone configurations as listed in the table on page 104.
These locations are considered as advanced programming, and they should only be changed if you
have a thorough understanding of the operation of each bit.
LOCATION 110 - CONFIGURATION GROUP 1 ALARM EVENT CODE (1 segment, numerical data)
Location 110 contains the event code that is sent for a Contact ID or SIA report. The desired event
code should be chosen from the Table 38 or Table 39 in Appendix 1. The zone ID will be the zone
that is in alarm.
This location is not used for slow speed formats (like 4+2 and 3+1). This location may also contain
the alarm report code for the Robofon format (value 00-99).
LOCATION 111 - CONFIGURATION GROUP 1 CHARACTERISTIC SELECT (5 segments, feature
selection data)
Segment 1
1 =
Fire
(turn on if this is a fire zone)
2
=
24 hour
(turn on for non-fire 24 hour zones)
3
=
Keyswitch
zone (normally open switch)
4
=
Follower
(turn on for burglary zones that are Instant during non-entry times)
5
=
Delay 1
zone (follows timer 1 Entry and Exit times)
6
=
Delay 2
zone (follows timer 2 Entry and Exit times)
7
=
Interior
(turn on if this zone should Automatically Bypass or Bypass for Stay
Arming)
8
=
Local only
(turn on if this zone should not be reported)
Remark: for a maintained keyswitch (ON/OFF), program both “keyswitch”
and “local”
Segment 2
1 =
On: if configuration group will
beep the keypad
for alarm
2
=
On: if configuration group will sound the
yelping siren
for alarm
3
=
On: if configuration group will sound the
steady siren
for alarm
4
=
On: if configuration group will
chime
5
=
On: if configuration group can be
bypassed
6
=
On: if configuration group is included in the
group shunt
Summary of Contents for NetworX V3
Page 1: ...NetworX Version 3 Alarm System Installation Manual 1070138 ...
Page 10: ...NetworX Version 3 Installation Manual 10 Section A Installing and programming a basic system ...
Page 50: ...NetworX Version 3 Installation Manual 50 Section B Programming the system ...
Page 257: ...NetworX Version 3 Installation Manual 257 Section C References ...