CHAPTER 2: INTRODUCTION
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
2–13
POWER METERING
Range:
-2000.000 to 2000.000 MW,
–2000.000 to 2000.000 Mvar,
0 to 2000.000 MVA
Accuracy at
I
avg
<
2
×
CT:
±1% of
×
2
×
CT
×
VT
ratio
×
VT
full-scale
Accuracy at
I
avg
>
2
×
CT:
±1.5% of
×
20
×
CT
×
VT
ratio
×
VT
full-scale
REACTIVE POWER
Block from online:
0 to 5000 s in steps of 1
Pickup level:
0.02 to 1.50
×
rated Mvar
(positive and negative)
Time delay:
0.2 to 120.0 s in steps of 0.1
Pickup accuracy:
see power metering
Timing accuracy:
±100ms or ±0.5% of total time
Elements:
Trip and Alarm
REVERSE POWER
Block from online:
0 to 5000 s in steps of 1
Pickup level:
0.02 to 0.99
×
rated MW
Time delay:
0.2 to 120.0 s in steps of 0.1
Pickup accuracy:
see power metering
Timing accuracy:
±100 ms or ±0.5% of total time
Elements:
Trip and Alarm
TRIP COIL SUPERVISION
Applicable voltage:
20 to 300 V DC/AC
Trickle current:
2 to 5 mA
2.2.6
Power Supply
CONTROL POWER
Options:
LO / HI (specify with order)
LO range:
20 to 60 V DC
20 to 48 V AC at 48 to 62 Hz
HI range:
90 to 300 V DC
70 to 265 V AC at 48 to 62 Hz
Power:
45 VA (max.), 25 VA typical
Total loss of voltage ride through time (0% control power): 16.7 ms
It is recommended that the 489 be powered up at least once per year to prevent
deterioration of electrolytic capacitors in the power supply.
FUSE
Current rating:
2.5 A
Type:
5x20mm HRC SLO-BLO Littelfuse
Model:
215-02.5
An external fuse must be used if the supply voltage exceeds 250 V
3