1–14
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 1: GETTING STARTED
If an entered setpoint value is out of range, the relay displays a message with the following
format:
In this case, 1 is the minimum setpoint value, 300 is the maximum, and 0.01 is the step
value. To have access to information on maximum, minimum, and step value, press the
HELP
key.
1.3.5
Output Relay Setpoints
The output relays 1 Trip and 5 Alarm can be associated to auxiliary relays 2 to 4. Each can
be selected individually, or in combination, in response to customer specific requirements.
These relays are initiated through the
ASSIGN ALARM RELAYS
or
ASSIGN TRIP RELAYS
setpoints specific to a protection element or function.
Z
Select the
S6 VOLTAGE ELEMENTS
Z
UNDERVOLTAGE
ZV
ASSIGN TRIP
RELAYS (1-4)
setpoint message.
If an application requires the undervoltage protection element to trip the 3 Auxiliary
relay,
Z
Select this output relay by pressing the “3” key; pressing the “3” key
again disables the 3 Auxiliary relay.
Enable/disable relays 1, 3, and 4 in the same manner until the desired
combination appear in the display.
Z
Press the
ENTER
key to store this change into memory.
As before, confirmation of this action will momentarily flash on the
display.
1.3.6
Text Setpoints
Text setpoints have data values, which are fixed in length, but user defined in character.
They may be comprised of uppercase letters, lowercase letters, numerals, and a selection
of special characters. The editing and storing of a text value is accomplished with the use
of the decimal [.],
VALUE
, and
ENTER
keys.
Press the
VALUE
keys until 115.00 : 1 is
displayed, or enter the value directly via the
numeric keypad.
VOLTAGE TRANSFORMER
RATIO: 115.0: 1
Press the
ENTER
key to store the setpoint.
NEW SETPOINT HAS
BEEN STORED
OUT-OF-RANGE! ENTER:
1-300:1 by 0.01:1
“1-300:1” indicates the range and “0.01:1” indicates the
step value
ASSIGN TRIP
RELAYS (1-4): 1---
ASSIGN TRIP
RELAYS (1-4): --3-
NEW SETPOINT HAS
BEEN STORED