5–42
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
FIGURE 5–5: Ground Directional Detection
5.6.10 High-Set Phase OC
PATH: SETPOINTS
ZV
S5 CURRENT ELEM.
ZV
HIGH-SET PHASE OVERCURRENT
If any individual phase current exceeds the pickup level for the specified trip time a trip will
occur if the feature is enabled. The element operates in both online and offline conditions.
This element can be used as a backup feature to other protection elements. In situations
where generators are connected in parallel this element would be set above the maximum
current contribution from the generator on which the protection is installed. With this
setting, the element would provide proper selective tripping. The basic operating time of
the element with no time delay is 50 ms at 50/60 Hz.
59G
A
A
C(B)
C(B)
B(C)
B(C)
TO 50:0.025
GROUND
INPUTS
50:0.025
I0
TO Vneutral OF EACH 489
AUXILIARY
CONTACT
GROUNDING SWITCH
808812A3.CDR
1 HIGH-SET
[
Z
]
PHASE OVERCURRENT
HIGH-SET PHASE O/C
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to
4
MESSAGE
HIGH-SET PHASE O/C
PICKUP: 5.00 x CT
Range: 0.15 to 20.00 x CT in steps of
0.01
MESSAGE
HIGH-SET PHASE O/C
DELAY: 1.00 s
Range: 0.00 to 100.00 s in steps of 0.01