489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
where
T
= trip time in seconds
D
=
NEUTRAL OVERVOLTAGE TRIP DELAY
setpoint
V
= neutral voltage
V
pickup
=
NEUTRAL O/V TRIP LEVEL
setpoint
The neutral overvoltage curves are shown below. Refer to Appendix B for Application
Notes.
FIGURE 5–8: Neutral Overvoltage Curves
FIGURE 5–9: Neutral Overvoltage Detection
Note
If the ground directional element is enabled, the Neutral Overvoltage element should be
coordinated with it. In cases of paralleled generator grounds through the same point, with
individual ground switches, per sketch below, it is recommended to use a ground switch
status function to prevent maloperation of the element.