CHAPTER 5: SETPOINTS
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–67
5.9.4
RTD 11
PATH: SETPOINTS
ZV
S8 RTD TEMPERATURE
ZV
RTD #11
RTD 11 defaults to Other RTD type. The Other selection allows the RTD to be used to
monitor any temperature that might be required, either for a process or additional
bearings or other. There are individual alarm and trip configurations for this RTD. Trip
voting has been added for extra reliability in the event of RTD malfunction. If enabled, a
second RTD must also exceed the trip temperature of the RTD being checked before a trip
will be issued. If the RTD is chosen to vote with itself, the voting feature is disabled. The RTD
name may be changed if desired.
5.9.5
RTD 12
PATH: SETPOINTS
ZV
S8 RTD TEMPERATURE
ZV
RTD #12
1 RTD #11
[
Z
]
RTD #11 APPLICATION:
Other
Range: Stator, Bearing, Ambient, Other,
None
MESSAGE
RTD #11 NAME:
Range: 8 alphanumeric characters
MESSAGE
RTD #11 ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to
5.
MESSAGE
RTD #11 ALARM
TEMPERATURE: 80°C
Range: 1 to 250°C in steps of 1
MESSAGE
RTD #11 ALARM
EVENTS: Off
Range: On, Off
MESSAGE
RTD #11 TRIP:
Off
Range: Off, Latched, Unlatched
MESSAGE
RTD #11 TRIP VOTING:
RTD #11
Range: RTD #1 to RTD #12
MESSAGE
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to
4
MESSAGE
RTD #11 TRIP
TEMPERATURE: 90°C
Range: 1 to 250°C in steps of 1
1 RTD #12
[
Z
]
RTD #12 APPLICATION:
Ambient
Range: Stator, Bearing, Ambient, Other,
None
MESSAGE
RTD #12 NAME:
Range: 8 alphanumeric characters
MESSAGE
RTD #12 ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to
5.