CHAPTER 1: GETTING STARTED
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
1–13
To set the ground CT ratio, modify the
S2 SYSTEM SETUP
Z
CURRENT SENSING
ZV
GROUND
CT RATIO
setpoint as shown below.
Z
Press the
MENU
key until the relay displays the setpoints menu header.
To set the VT connection type and ratings, modify the
S2 SYSTEM SETUP
ZV
VOLTAGE
SENSING
ZV
VT CONNECTION TYPE
and the
S2 SYSTEM SETUP
ZV
VOLTAGE SENSING
ZV
VOLTAGE TRANSFORMER RATIO
setpoints as shown below.
Z
Press the
MENU
key until the relay displays the setpoints menu header.
SETPOINTS
[
Z
]
Press
MESSAGE
X
or
ENTER
SETPOINTS
[
Z
]
S1 489 SETUP
Press
MESSAGE
T
SETPOINTS
[
Z
]
S2 SYSTEM SETUP
Press
MESSAGE
X
or
ENTER
CURRENT
[
Z
]
SENSING
Press
MESSAGE
X
or
ENTER
PHASE CT PRIMARY:
600 A
Press
MESSAGE
T
GROUND CT:
1 A Secondary
Press
MESSAGE
T
GROUND CT RATIO:
100: 1
Press the
VALUE
keys until 200: 1 is displayed,
or enter the value directly via the numeric
keypad.
GROUND CT RATIO:
200: 1
Press the
ENTER
key to store the setpoint.
NEW SETPOINT HAS
BEEN STORED
SETPOINTS
[
Z
]
Press
MESSAGE
X
or
ENTER
SETPOINTS
[
Z
]
S1 489 SETUP
Press
MESSAGE
T
SETPOINTS
[
Z
]
S2 SYSTEM SETUP
Press
MESSAGE
X
or
ENTER
CURRENT
[
Z
]
SENSING
Press
MESSAGE
T
VOLTAGE
[
Z
]
SENSING
Press
MESSAGE
X
or
ENTER
VT CONNECTION TYPE:
None
Press the
VALUE
keys until
“Open Delta” is displayed.
VT CONNECTION TYPE:
Open Delta
Press the
ENTER
key to store the setpoint.
NEW SETPOINT HAS
BEEN STORED
Press
MESSAGE
T
VOLTAGE TRANSFORMER
RATIO: 5.00: 1