CHAPTER 5: SETPOINTS
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–65
5.9.2
RTDs 1 to 6
PATH: SETPOINTS
ZV
S8 RTD TEMPERATURE
ZV
RTD #1(6)
RTDs 1 through 6 default to Stator RTD type. There are individual alarm and trip
configurations for each RTD. This allows one of the RTDs to be turned off if it malfunctions.
The alarm level is normally set slightly above the normal running temperature. The trip
level is normally set at the insulation rating. Trip voting has been added for extra reliability
in the event of RTD malfunction. If enabled, a second RTD must also exceed the trip
temperature of the RTD being checked before a trip will be issued. If the RTD is chosen to
vote with itself, the voting feature is disabled. Each RTD name may be changed if desired.
180
356
168.47
280.77
233.97
16.00
190
374
172.46
291.96
243.30
16.39
200
392
175.84
303.46
252.88
16.78
210
410
179.51
315.31
262.76
17.17
220
428
183.17
327.54
272.94
17.56
230
446
186.82
340.14
283.45
17.95
240
464
190.45
353.14
294.28
18.34
250
482
194.08
366.53
305.44
18.73
Table 5–6: RTD Temperature vs. Resistance
Temperature
100
Ω
Pt
(DIN 43760)
120
Ω
Ni
100
Ω
Ni
10
Ω
Cu
° C
° F
1 RTD #1
[
Z
]
RTD #1 APPLICATION:
Stator
Range: Stator, Bearing, Ambient, Other,
None
MESSAGE
RTD #1 NAME:
Range: 8 alphanumeric characters
MESSAGE
RTD #1 ALARM:
Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to
5.
MESSAGE
RTD #1 ALARM
TEMPERATURE: 130°C
Range: 1 to 250°C in steps of 1
MESSAGE
RTD #1 ALARM
EVENTS: Off
Range: On, Off
MESSAGE
RTD #1 TRIP:
Off
Range: Off, Latched, Unlatched
MESSAGE
RTD #1 TRIP VOTING:
RTD #1
Range: RTD #1 to RTD #12
MESSAGE
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to
4
MESSAGE
RTD #1 TRIP
TEMPERATURE: 155°C
Range: 1 to 250°C in steps of 1