CHAPTER 5: SETPOINTS
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–91
5.11.3 Trip Coil Monitor
PATH: SETPOINTS
ZV
S10 MONITORING
ZV
TRIP COIL MONITOR
If the trip coil monitor alarm feature is enabled as latched or unlatched, the trip coil
supervision circuitry will monitor the trip coil circuit for continuity any time that the breaker
status input indicates that the breaker is closed. If that continuity is broken, a trip coil
monitor alarm will occur in approximately 300 ms.
If 52 Open/Closed is selected, the trip coil supervision circuitry monitors the trip coil circuit
for continuity at all times regardless of breaker state. This requires an alternate path
around the 52a contacts in series with the trip coil when the breaker is open. See the figure
below for modifications to the wiring and proper resistor selection. If that continuity is
broken, a Starter Failure alarm will indicate Trip Coil Supervision.
FIGURE 5–25: Trip Coil Supervision
TRIP COIL
[
Z
]
MONITOR
TRIP COIL MONITOR
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to
5
MESSAGE
SUPERVISION OF TRIP
COIL: 52 Closed
Range: 52 Closed, 52 Open/Closed
MESSAGE
TRIP COIL MONITOR
ALARM EVENTS: Off
Range: On, Off
808727A1.CDR
VALUE OF RESISTOR 'R'
SUPPLY
OHMS
WATTS
48 VDC
12
5
VDC
2
5
0 VDC
10 K
2
5
K
5
0 K
2
5
5
TRIP
COIL
TRIP COIL
SUPERVISION
R1 TRIP
CONTACT
F11
E2
F1
E11
5
2a
TRIP COIL CLOSED SUPERVISION
"52 Closed"
TRIP COIL
SUPERVISION
R1 TRIP
CONTACT
TRIP
COIL
F11
E2
F1
E11
5
2a
TRIP COIL OPEN/CLOSED SUPERVISION
"52 Open/Closed"
5
2a
TRIP
COIL
TRIP COIL
SUPERVISION
R1 TRIP
CONTACT
F11
E2
F1
E11
5
2a
TRIP COIL
OPEN/CLOSED
SUPERVISION
"52 Open/Closed"
WITH MULTIPLE
BREAKER AUX
CONTACTS