![GE Multilin 489 Instruction Manual Download Page 220](http://html.mh-extra.com/html/ge/multilin-489/multilin-489_instruction-manual_123013220.webp)
6–6
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
The range for the
CAUSE OF LAST TRIP
setpoint is: No Trip to Date, General Inputs A to G,
Sequential Trip, Field-Bkr Discrep., Tachometer, Thermal Model, Offline Overcurrent, Phase
Overcurrent, Neg. Seq. Overcurrent, Ground Overcurrent, Phase Differential, RTDs 1 to 12,
Overvoltage, Undervoltage, Volts/Hertz, Phase Reversal, Underfrequency, Overfrequency,
Neutral O/V, Neutral U/V (3rd), Reactive Power, Reverse Power, Low Forward Power,
Inadvertent Energ., and Analog Inputs 1 to 4.
Immediately prior to issuing a trip, the 489 takes a snapshot of generator parameters and
stores them as pre-trip values; this allows for troubleshooting after the trip occurs. The
cause of last trip message is updated with the current trip and the screen defaults to that
message. All trip features are automatically logged as date and time stamped events as
they occur. This information can be cleared using the
S1 489 SETUP
ZV
CLEAR DATA
ZV
CLEAR LAST TRIP DATA
setpoint. If the cause of last trip is “No Trip To Date”, the subsequent
pretrip messages will not appear. Last Trip Data will not update if a digital input
programmed as Test Input is shorted.
6.2.4
Alarm Status
PATH: ACTUAL VALUES
Z
A1 STATUS
ZV
ALARM STATUS
MESSAGE
AMBIENT RTD
RTD#12: 0°C PreTrip
Range: –50 to 250°C. Seen only if at
least one RTD is Ambient
MESSAGE
ANALOG INPUT 1
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
ANALOG INPUT 1
is “Disabled”
MESSAGE
ANALOG INPUT 2
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
ANALOG INPUT 2
is “Disabled”
MESSAGE
ANALOG INPUT 3
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
ANALOG INPUT 3
is “Disabled”
MESSAGE
ANALOG INPUT 4
PreTrip: 0 Units
Range: –50000 to 50000. Not seen if
ANALOG INPUT 4
is “Disabled”
MESSAGE
Vab/Iab PreTrip:
0.0
Ω
sec.
0°
Range: 0 to 65535
Ω
sec.; 0 to 359°.
Seen only if Loss of Excitation is
enabled
NOTE
ALARM STATUS
[
Z
]
NO ALARMS
Range: N/A. Message seen when no
alarms are active
MESSAGE
Input A ALARM
STATUS: Active
Range: Active, Latched. See Note
below.
MESSAGE
Input B ALARM
STATUS: Active
Range: Active, Latched. See Note
below.
MESSAGE
Input C ALARM
STATUS: Active
Range: Active, Latched. See Note
below.
MESSAGE
Input D ALARM
STATUS: Active
Range: Active, Latched. See Note
below.
MESSAGE
Input E ALARM
STATUS: Active
Range: Active, Latched. See Note
below.