GE Power Management
469 Motor Management Relay
4-23
4 SETPOINT PROGRAMMING
4.4 S3 DIGITAL INPUTS
4
4.4.18 DIGITAL INPUT FUNCTION: GENERAL SWITCH A-D
There are four General Switch functions assignable to any of the four assignable digital inputs. Once a General
Switch function is chosen for one of the digital inputs, the setpoint messages shown here follow the assign-
ment message. An alarm and/or trip may then be configured for that input. The alarm and/or trip may be
assigned a common name and a common block time from motor start if required (if the alarm is to be disabled
until some period of time after he motor has been started). A value of
"0"
for the
BLOCK TIME
indicates that the
feature is always active, when the motor is stopped or running. The switch may also be defined as normally
open or normally closed. After the block delay has expired, the digital input will be monitored. If the switch is
not in its normal state after the specified delay, an alarm or trip will occur.
4.4.19 DIGITAL INPUT FUNCTION: CAPTURE TRACE
This setting allows the user to capture a trace upon command via a switch input. The captured waveforms can
then be displayed with the 469PC software.
4.4.20 DIGITAL INPUT FUNCTION: SIMULATE PRE-FAULT
This setting allows the user to start Simulate Pre-Fault mode as programmed in S13 via a switch input. This is
typically used for relay or system testing.
4.4.21 DIGITAL INPUT FUNCTION: SIMULATE FAULT
This setting allows the user to start Simulate Fault mode as programmed in S13 via a switch input. This is typ-
ically used for relay or system testing.
4.4.22 DIGITAL INPUT FUNCTION: SIMULATE PRE-FAULT…FAULT
This setting allows the user to start Simulate Pre-Fault to Fault mode as programmed in S13 via a switch input.
This is typically used for relay or system testing.
SWITCH NAME:
General Sw. A
Range: 12 alphanumeric characters
GENERAL SWITCH A:
Normally Open
Range: Normally Open, Normally Closed
BLOCK INPUT
FROM START: 0 s
Range:
0 to 5000 sec., step 1 (0 indicates that feature is active
while motor is stopped as well as running)
GENERAL SWITCH A
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM RELAYS:
Alarm
Range:
Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3, Alarm
& Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
GENERAL SWITCH A
ALARM DELAY: 5.0 s
Range: 0.1 to 5000.0 sec., step 0.1
GENERAL SWITCH A
EVENTS: Off
Range: On, Off
GENERAL SWITCH A
TRIP: Off
Range: Off, Latched, Unlatched
ASSIGN TRIP RELAYS:
Trip
Range:
Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
GENERAL SWITCH A
TRIP DELAY: 5.0 s
Range: 0.1 to 5000.0 sec., step 0.1