GE Power Management
469 Motor Management Relay
5-5
5 ACTUAL VALUES
5.2 A1 STATUS
5
5.2.3 ALARM STATUS
y
ALARM STATUS
y
[ENTER] for more
NO ALARMS
Range: N/A
Message seen when no alarms are active
REMOTE ALARM
STATUS: Active
Range:
Active, Latched. The first line of this message reflects
the Switch Name as programmed. The status is Active if
the condition that caused the alarm is still present
PRESSURE SWITCH
ALARM STATUS: Active
Range: Active, Latched
Status is Active if condition causing the Alarm still present
VIBRATION SWITCH
ALARM STATUS: Active
Range: Active, Latched
Status is Active if condition causing the Alarm still present
DIG. COUNTER ALARM:
1 000 000 000 Units
Range: 1 to 9999999999
Displays current value of digital counter
TACHOMETER
ALARM: 3000 RPM
Range: 0 to 3600 RPM
Current Tachometer Digital Input value is shown here
GENERAL SW. A
ALARM STATUS: Active
Range:
Active, Latched. The first line of this message reflects
the Switch Name as programmed. The status is Active if
the condition that caused the alarm is still present
THERMAL CAPACITY
ALARM: 100% USED
Range: 1 to 100.
Thermal Capacity Used value is shown here
XX.XX x FLA OVERLOAD
TIME TO TRIP: XXXXX s
Range: 0 to 99999 sec.
Overload level and estimated time to trip are shown here
UNDERCURRENT ALARM
Ia = 85 A
85% FLA
Range: 1 to 5000 A; 5 to 99% FLA
Value of lowest phase current is shown here
CURRENT UNBALANCE
ALARM: 15%
Range: 0 to 100%
Reflects the present unbalance level
GROUND FAULT
ALARM: 25.3 A
Range: 0.1 to 5000 A
Reflects the present ground current level
STATOR RTD #1
ALARM: 135°C
Range:
–50 to 250°C. The first line of this alarm message
reflects the RTD Name as programmed. Reflects
present RTD temperature
OPEN SENSOR ALARM:
RTD # 1 2 3 4 5 6...
Range:
the RTD number with the open sensor as programmed
for RTDs 1 to 12
SHORT/LOW TEMP ALARM
RTD # 7 8 9 10 11...
Range: 1 to 12
Reflects the RTD with the short/low temperature alarm
UNDERVOLTAGE ALARM
Vab= 3245 V 78% Rated
Range: 0 to 20000 V; 50 to 99% of Rated
Value of lowest line-to-line voltage is shown here
OVERVOLTAGE ALARM
Vab= 4992 V 120%
Range: 0 to 20000 V; 101 to 150% of Rated
Value of lowest line-to-line voltage is shown here
SYSTEM FREQUENCY
ALARM: 59.4 Hz
Range: 0.00, 20.00 to 120.00 Hz
System voltage frequency value is shown here
POWER FACTOR
ALARM PF: 0.00
Range: 0.00 to 0.99 Lead or Lag, 0.00, 1.00
Current Power Factor is shown here
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE