4-86
469 Motor Management Relay
GE Power Management
4.14 S13 469 TESTING
4 SETPOINT PROGRAMMING
4
4.14.4 TEST OUTPUT RELAYS
In addition to the simulation modes, the
TEST OUTPUT RELAYS
setpoint group may be used during startup or test-
ing to verify that the output relays are functioning correctly.
The output relays can only be forced to operate only if the motor is stopped and there are no trips, alarms, or
start blocks active. If any relay is forced to operate, the relay will toggle from its normal state when there are no
trips, alarms, or blocks to its active state. The appropriate relay indicator will illuminate at that time. Selecting
"Disabled"
places the output relays back in service. If the 469 measures phase current or control power is
cycled, the
FORCE OPERATION OF RELAYS
setpoint will automatically become disabled and the output relays will
revert back to their normal states.
If any relay is forced, the 469 In Service LED will flash, indicating that the 469 is not in protection mode.
4.14.5 TEST ANALOG OUTPUT
In addition to the simulation modes, the
TEST ANALOG OUTPUT
setpoint group may be used during startup or
testing to verify that the analog outputs are functioning correctly.
The analog outputs can only be forced if the motor is stopped and there are no trips, alarms, or start blocks
active. When the
FORCE ANALOG OUTPUTS FUNCTION
is
"Enabled"
, the output reflects the forced value as a per-
centage of the 4 to 20 mA or 0 to 1 mA range. Selecting
"Disabled"
places all four analog output channels back
in service, reflecting the parameters programmed to each. If the 469 measures phase current or control power
is cycled, the
FORCE ANALOG OUTPUTS FUNCTION
is automatically disabled and all analog outputs revert back to
their normal state.
Any time the analog outputs are forced, the 469 In Service LED will flash, indicating that the 469 is not in pro-
tection mode.
y
TEST OUTPUT RELAYS
y
[ENTER] for more
FORCE OPERATION OF
RELAYS: Disabled
Range:
Disabled, R1 Trip, R2 Auxiliary, R3 Auxiliary, R4 Alarm,
R5 Block, R6 Service, All Relays, No Relays
y
TEST ANALOG OUTPUT
y
[ENTER] for more
FORCE ANALOG OUTPUTS
FUNCTION: Disabled
Range: Enabled, Disabled
ANALOG OUTPUT 1
FORCED VALUE: 0%
Range: 0 to 100%, step 1
ANALOG OUTPUT 2
FORCED VALUE: 0%
Range: 0 to 100%, step 1
ANALOG OUTPUT 3
FORCED VALUE: 0%
Range: 0 to 100%, step 1
ANALOG OUTPUT 4
FORCED VALUE: 0%
Range: 0 to 100%, step 1
ENTER
ESCAPE
ð
ð
ENTER
ESCAPE
ð
ð
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE
MESSAGE
ESCAPE