4.11 S10 POWER ELEMENTS
4 SETPOINT PROGRAMMING
4
4.11.3 REACTIVE POWER
If the 469 is applied on a synchronous motor, it is desirable not to trip or alarm on kvar until the field has been
applied. Therefore, this feature can be blocked until the motor comes up to speed and the field is applied. From
that point forward, the kvar trip and alarm elements will be active. Once the kvar level exceeds either the posi-
tive or negative level, for the specified delay, a trip or alarm will occur indicating a positive or negative kvar con-
dition. The reactive power alarm can be used to detect loss of excitation and out of step.
y
REACTIVE POWER
y
[ENTER] for more
BLOCK kvar ELEMENT
FROM START: 1 s
Range: 0 to 5000 sec., step 1
REACTIVE POWER
ALARM: Off
Range: Off, Latched, Unlatched
ASSIGN ALARM RELAYS:
Alarm
Range:
Alarm, Alarm & Auxiliary2, Alarm & Aux2 & Aux3,
Alarm & Auxiliary3, Auxiliary2, Aux2 & Aux3, Auxiliary3
POSITIVE kvar ALARM
LEVEL: 10 kvar
Range: 1 to 25000 kvar, step 1
NEGATIVE kvar ALARM
LEVEL: 10 kvar
Range: 1 to 25000 kvar, step 1
REACTIVE POWER ALARM
DELAY: 1.0 s
Range: 0.2 to 30.0 sec., step: 0.1
REACTIVE POWER ALARM
EVENTS: Off
Range: On, Off
REACTIVE POWER
TRIP: Off
Range: Off, Latched, Unlatched
ASSIGN TRIP RELAYS:
Trip
Range:
Trip, Trip & Auxiliary2, Trip & Aux2 & Aux3,
Trip & Auxiliary3
POSITIVE kvar TRIP
LEVEL: Off
Range: 1 to 25000 kvar, step 1
NEGATIVE kvar TRIP
LEVEL: Off
Range: 1 to 25000 kvar, step 1
REACTIVE POWER TRIP
DELAY: 1.0 s
Range: 0.2 to 30.0 sec., step: 0.1