GE Power Management
469 Motor Management Relay
2-3
2 INSTALLATION
2.1 MECHANICAL
2
2.1.3 INSTALLATION
The 469 case, alone or adjacent to another SR series unit, can be installed in the panel of a standard 19-inch
rack (see the diagram below for panel cutout dimensions). Provision must be made when mounting for the
front door to swing open without interference to, or from, adjacent equipment. Normally the 469 unit is mounted
in its case when shipped from the factory, and should be removed before mounting the case in the supporting
panel. Unit withdrawal is described in the next section.
Figure 2–4: SINGLE AND DOUBLE 469 CUTOUT PANELS
After the mounting hole in the panel has been prepared, slide the 469 case into the panel from the front. Apply-
ing firm pressure on the front to ensure the front bezel fits snugly against the front of the panel, bend out the
pair of retaining tabs (to a horizontal position) from each side of the case as shown below. The case is now
securely mounted, ready for panel wiring. If additional support is desired, the SR optional mounting kit may be
ordered.
Figure 2–5: BEND UP MOUNTING TABS
Single Cutout Panel
Double Cutout Panel