2-4
469 Motor Management Relay
GE Power Management
2.1 MECHANICAL
2 INSTALLATION
2
2.1.4 UNIT WITHDRAWAL AND INSERTION
TURN OFF CONTROL POWER BEFORE DRAWING OUT OR RE-INSERTING THE RELAY TO
PREVENT MALOPERATION!
If an attempt is made to install a unit into a non-matching case, the mechanical key will pre-
vent full insertion of the unit. Do not apply strong force in the following step or damage may
result.
To remove the unit from the case:
1.
Open the cover by grasping the center of the right side and then pulling the cover, which will rotate about
the hinges on the left.
2.
Release the locking latch, located below the locking handle, by pressing upward on the latch with the tip of
a screwdriver.
Figure 2–6: PRESS LATCH TO DISENGAGE HANDLE
3.
While holding the latch raised, grasp the locking handle in the center and pull firmly, rotating the handle up
from the bottom of the unit until movement ceases.
Figure 2–7: ROTATE HANDLE TO STOP POSITION
CAUTION