5.5 A4 MAINTENANCE
5 ACTUAL VALUES
5
5.5.2 GENERAL COUNTERS
Two of the 469 general counters count the number of motor starts or start attempts and the number of Emer-
gency Restarts performed to start a given motor over time. This may be useful information when troubleshoot-
ing a motor failure. When either of these counters reaches 50000, that counter will reset to 0. This information
can be cleared with the
S1 469 SETUP\INSTALLATION\RESET MOTOR INFORMATION
setpoint. Another of the 469
General counters will count the number of starter operations performed over time. This counter is incremented
any time the motor is stopped, either by a trip or normal stop. This may be useful information for starter mainte-
nance. When the counter reaches 50000, that counter will reset to 0. This information may be cleared with the
S1 469 SETUP\INSTALLATION\RESET STARTER INFORMATION
setpoint. If one of the assignable digital inputs is pro-
grammed as
Digital Counter
, that counter measurement will appear here. The counter can be reset to zero if the
counter is of the incrementing type or pre-set to a predetermined value using the
S1 469 SETUP\CLEAR DATA\PRE-
SET DIGITAL COUNTER
setpoint.
5.5.3 TIMERS
One of the 469 timers accumulates the total running time for the Motor. This may be useful for scheduling rou-
tine maintenance. When this timer reaches 100000, it will reset to 0. This timer can be cleared using the
S1 469
SETUP \ INSTALLATION \ RESET MOTOR INFORMATION
setpoint.
The
TIME BETWEEN STARTS TIMER
value may be viewed here. This value might be useful for planning a motor
shutdown. The
STARTS/HOUR TIMER
value is also viewable here.
y
GENERAL COUNTERS
y
[ENTER] for more
NUMBER OF MOTOR
STARTS: 0
Range: 0 to 50000
NUMBER OF EMERGENCY
RESTARTS: 0
Range: 0 to 50000
NUMBER OF STARTER
OPERATIONS: 0
Range: 0 to 50000
DIGITAL COUNTER
0 Units
Range:
0 to 1 000 000 000. Seen only if an Assignable Digital
Input programmed as Digital Counter.
y
TIMERS
y
[ENTER] for more
MOTOR RUNNING HOURS:
0 hr
Range: 0 to 100000 hrs.
TIME BETWEEN STARTS
TIMER: 0 min
Range: 0 to 500 min.
STARTS/HOUR TIMERS
0 0 0 0 0 min
Range: 0 to 60 min.