GE Power Management
469 Motor Management Relay
6-41
6 COMMUNICATIONS
6.4 MEMORY MAP
6
RTD #6
continued
1839
1st and 2nd char. of RTD #6 Name
0
65535
1
-
F22
‘ ‘
...
183C
7th and 8th char. of RTD #6 Name
0
65535
1
-
F22
‘ ‘
183D
Reserved
...
184D
Reserved
184E
RTD #6 Alarm Temperature (in Fahrenheit)
34
482
1
°F
F1
266
184F
RTD #6 Trip Temperature (in Fahrenheit)
34
482
1
°F
F1
311
RTD #7
1850
RTD #7 Application
0
4
1
-
FC121
2
1851
RTD #7 Alarm
0
2
1
-
FC115
0
1852
RTD #7 Alarm Relays
0
6
1
-
FC113
0
1853
RTD #7 Alarm Temperature
1
250
1
°C
F1
80
1854
RTD #7 Alarm Events
0
1
1
-
FC103
0
1855
RTD #7 Trip
0
2
1
-
FC115
0
1856
RTD #7 Trip Voting
1
12
1
-
FC122
7
1857
RTD #7 Trip Relays
0
3
1
-
FC111
0
1858
RTD #7 Trip Temperature
1
250
1
°C
F1
90
1859
1st and 2nd char. of RTD #7 Name
0
65535
1
-
F22
‘ ‘
...
185C
7th and 8th char. of RTD #7 Name
0
65535
1
-
F22
‘ ‘
185D
Reserved
...
186D
Reserved
186E
RTD #7 Alarm Temperature (in Fahrenheit)
34
482
1
°F
F1
176
186F
RTD #7 Trip Temperature (in Fahrenheit)
34
482
1
°F
F1
194
RTD #8
1870
RTD #8 Application
0
4
1
-
FC121
2
1871
RTD #8 Alarm
0
2
1
-
FC115
0
1872
RTD #8 Alarm Relays
0
6
1
-
FC113
0
1873
RTD #8 Alarm Temperature
1
250
1
°C
F1
80
1874
RTD #8 Alarm Events
0
1
1
-
FC103
0
1875
RTD #8 Trip
0
2
1
-
FC115
0
1876
RTD #8 Trip Voting
1
12
1
-
FC122
8
1877
RTD #8 Trip Relays
0
3
1
-
FC111
0
1878
RTD #8 Trip Temperature
1
250
1
°C
F1
90
1879
1st and 2nd char. of RTD #8 Name
0
65535
1
-
F22
‘ ‘
...
187C
7th and 8th char. of RTD #8 Name
0
65535
1
-
F22
‘ ‘
187D
Reserved
...
188D
Reserved
188E
RTD #8 Alarm Temperature (in Fahrenheit)
34
482
1
°F
F1
176
188F
RTD #8 Trip Temperature (in Fahrenheit)
34
482
1
°F
F1
194
Table 6–1: 469 MEMORY MAP (Sheet 24 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE