GE Power Management
469 Motor Management Relay
6-23
6 COMMUNICATIONS
6.4 MEMORY MAP
6
TEMPERA-
TURE
continued
0329
RTD #9 Temperature
–50
250
1
°C
F4
0
032A
RTD #10 Temperature
–50
250
1
°C
F4
0
032B
RTD #11 Temperature
–50
250
1
°C
F4
0
032C
RTD #12 Temperature
–50
250
1
°C
F4
0
032D
Reserved
032E
Reserved
032F
Reserved
0330
Hottest Stator RTD (in Fahrenheit)
–58
482
1
°F
F4
32
0331
RTD #1 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0332
RTD #2 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0333
RTD #3 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0334
RTD #4 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0335
RTD #5 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0336
RTD #6 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0337
RTD #7 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0338
RTD #8 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
0339
RTD #9 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
033A
RTD #10 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
033B
RTD #11 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
033C
RTD #12 Temperature (in Fahrenheit)
–58
482
1
°F
F4
32
033D
Reserved
033E
Reserved
033F
Reserved
VOLTAGE
METERING
0340
Vab
0
20000
1
V
F1
0
0341
Vbc
0
20000
1
V
F1
0
0342
Vca
0
20000
1
V
F1
0
0343
Average Line Voltage
0
20000
1
V
F1
0
0344
Van
0
20000
1
V
F1
0
0345
Vbn
0
20000
1
V
F1
0
0346
Vcn
0
20000
1
V
F1
0
0347
Average_Phase_Voltage
0
20000
1
V
F1
0
0348
System Frequency
0
12000
1
Hz
F3
0
0349
Reserved
...
...
035F
Reserved
SPEED
0360
Tachometer RPM
0
3600
1
RPM
F1
0
0361
Reserved
...
...
036F
Reserved
POWER
METERING
0370
Power Factor
–99
100
1
-
F21
0
0371
Real Power
–99999
99999
1
kW
F12
0
0373
Real Power (HP)
0
65535
1
hp
F1
0
0374
Reactive Power
–99999
99999
1
kvar
F12
0
Table 6–1: 469 MEMORY MAP (Sheet 6 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT