GE Power Management
469 Motor Management Relay
6-37
6 COMMUNICATIONS
6.4 MEMORY MAP
6
CURRENT
UNBALANCE
1680
Current Unbalance Alarm
0
2
1
-
FC115
0
1681
Current Unbalance Alarm Relays
0
6
1
-
FC113
0
1682
Current Unbalance Alarm Pickup
4
40
1
%
F1
15
1683
Current Unbalance Alarm Delay
1
60
1
s
F1
1
1684
Current Unbalance Alarm Events
0
1
1
-
FC103
0
1685
Current Unbalance Trip
0
2
1
-
FC115
0
1686
Current Unbalance Trip Relays
0
3
1
-
FC111
0
1687
Current Unbalance Trip Pickup
4
40
1
%
F1
20
1688
Current Unbalance Trip Delay
1
60
1
s
F1
1
1689
Reserved
...
169F
Reserved
GROUND
FAULT
16A0
Reserved
16A1
Ground Fault Alarm
0
2
1
-
FC115
0
16A2
Ground Fault Alarm Relays
0
6
1
-
FC113
0
16A3
Ground Fault Alarm Pickup
10
100
1
×
CT
F3
10
16A4
Alarm Pickup for 50/0.025 CT
25
2500
1
A
F3
100
16A5
Intentional GF Alarm Delay
0
1000
10
ms
F1
0
16A6
Ground Fault Alarm Events
0
1
1
-
FC103
0
16A7
Ground Fault Trip
0
2
1
-
FC115
0
16A8
Ground Fault Trip Relays
0
6
1
-
FC118
0
16A9
Ground Fault Trip Pickup
10
100
1
×
CT
F3
20
16AA
Trip Pickup for 50/0.025 CT
25
2500
1
A
F3
100
16AB
Intentional GF Trip Delay
0
1000
10
ms
F1
0
16AC
Ground Fault Trip Backup
0
1
1
-
FC103
0
16AD
Ground Fault Trip Backup Relays
0
2
1
-
FC119
0
16AE
Ground Fault Trip Backup Delay
10
2000
10
ms
F1
200
...
Reserved
16BF
Reserved
PHASE
DIFFERENTIAL
16C0
Phase Differential Trip
0
2
1
-
FC115
0
16C1
Phase Differential Trip Relays
0
6
1
-
FC118
0
16C2
Differential Trip Pickup While Starting
5
100
1
×
CT
F3
10
16C3
Differential Trip Delay While Starting
0
60000
10
ms
F1
0
16C4
Differential Trip Pickup While Running
5
100
1
×
CT
F3
10
16C5
Differential Trip Delay While Running
0
1000
10
ms
F1
0
16C4
Reserved
...
16CF
Reserved
Table 6–1: 469 MEMORY MAP (Sheet 20 of 43)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT