The menu is shown on the front panel upon successful login of the Administrator role.
The
LOGIN
setting in this menu is similar to that described in
SETTINGS > PRODUCT SETUP > SECURITY
except for the factory
role.
Passwords are stored in text format. No encryption is applied.
Session settings
SETTINGS
PRODUCT SETUP
SECURITY
SESSION SETTINGS
SESSION LOCKOUT
— This setting specifies the number of failed authentications before the device blocks subsequent
authentication attempts for the lockout period. A value of zero means lockout is disabled.
SESSION LOCKOUT PERIOD
— This setting specifies the period of time in minutes of a lockout period. A value of 0 means that
there is no lockout period.
Restore defaults
SETTINGS
PRODUCT SETUP
SECURITY
RESTORE DEFAULTS
LOAD FACTORY DEFAULTS
— This setting is used to reset all the settings, communication, and security passwords. An
Administrator role is used to change this setting and a Supervisor role (if not disabled) approves it.
Supervisory
SETTINGS
PRODUCT SETUP
SECURITY
SUPERVISORY
NEW PASSWORD:
Range: 20 alphanumeric characters
CONFIRM PASSWORD:
Range: 20 alphanumeric characters
In Device authentication mode, the Observer role does not have a password associated with it. In Server
authentication mode the Observer role requires a password.
If you are locked out of the software, contact GE Grid Solutions for the default password. When using CyberSentry,
the default password is "ChangeMe1#".
Once the passwords are set, the Administrator with Supervisor approval can change the role-associated password.
In CyberSentry, password encryption is not supported.
SESSION
SETTINGS
SESSION LOCKOUT:
3
Range: 0 to 99
SESSION LOCKOUT
PERIOD: 3 min
Range: 0 to 9999 minutes
RESTORE DEFAULTS
LOAD FACTORY
DEFAULTS: No
Range: Yes, No
SUPERVISORY
DEVICE
AUTHENTICATION: Yes
Range: Yes, No
BYPASS ACCESS:
Disabled
Range: Local, Remote, Local and Remote, Disabled,
Pushbuttons
LOCK RELAY:
Disabled
Range: Enabled, Disabled
FACTORY SERVICE
MODE: Disabled
Range: Enabled, Disabled
SELF TESTS
See below
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...