10-8
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
BACK UP AND RESTORE SETTINGS
CHAPTER 10: MAINTENANCE
10
10.6.2 Compare two devices
Preferences are set under
File > Preferences
as follows:
•
Comparison Report: Sequential File 1, File 2 Layout
— When disabled (default), the report shows only what differs, as
shown in the previous figure. When enabled, the report indicates differences by device.
Figure 10-8: Device settings compared between two devices, displayed sequentially
There are two ways to compare devices: devices in the Offline area or between Online and Offline devices.
To compare settings of two devices in the Offline Window area:
1.
Right-click a first device in the Offline Window area and select
Compare Two Devices
.
2.
In the window that opens, select a second device and click the
Receive
button. The file generates and the number of
differences displays.
3.
To save the report, click
File > Save As
, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.
To compare settings between Online and Offline devices:
1.
Right-click a device in the Online Window area and select
Compare with Device
.
2.
In the window that opens, enter a path/file name at the bottom o f the window.
3.
Select the second device.
4.
Click the
OK
button. The file generates, and the differences are highlighted in red, which is for the first device.
10.7 Back up and restore settings
Back up a copy of the in-service settings for each commissioned UR device, so as to revert to the commissioned settings
after inadvertent, unauthorized, or temporary setting changes are made, after the settings defaulted due to firmware
upgrade, or when the device has to be replaced. This section describes how to backup settings to a file and how to use
that file to restore the settings to the original relay or to a replacement relay.
10.7.1 Back up settings
The following file types can be saved:
•
URS — UR settings file — When the IEC 61850 option is not present
•
IID — Instantiated IED capability description file — Actual settings on UR
•
ICD — IED Capability Description file — Default settings on UR
•
CID — Configured IED description file — Settings sent to the UR (may or may not contain the present settings)
UR device settings can be saved in a backup URS file using the EnerVista UR Setup software. The URS file is the standard
UR settings file. For an introduction to settings files in the URS format, see the beginning of the Interfaces chapter.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...