5-12
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
If setting access is
not
authorized for local operation (front panel or RS232 interface) and the user attempts to obtain
setting access, then the UNAUTHORIZED ACCESS message displays on the front panel.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
•
REMOTE SETTING AUTH
— This setting is used for remote (Ethernet or RS485 interface) setting access supervision.
If this setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is
required. If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is
provided. If this setting is any other FlexLogic operand, then the operand must be asserted (set as on) prior to
providing the remote setting password to gain setting access.
If this setting is "Off," firmware upgrades are blocked. If this setting is "On," firmware upgrades are allowed.
•
ACCESS AUTH TIMEOUT
— This setting represents the timeout delay for local setting access. This setting is applicable
when the
LOCAL SETTING AUTH
setting is programmed to any operand except “On.” The state of the FlexLogic operand
is monitored continuously for an off-to-on transition. When this occurs, local access is permitted and the timer
programmed with the
ACCESS AUTH TIMEOUT
setting value is started. When this timer expires, local setting access is
immediately denied. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the
timeout is restarted. The status of this timer updates every five seconds.
The following settings are available through the remote (EnerVista UR Setup) interface only. Select the
Settings > Product
Setup > Security
menu item to display the security settings window.
The
Remote Settings Authorized
setting is used for remote (Ethernet or RS485 interface) setting access supervision. If this
setting is “On” (the default setting), then remote setting access functions as normal; that is, a remote password is required.
If this setting is “Off,” then remote setting access is blocked even if the correct remote setting password is provided. If this
setting is any other FlexLogic operand, then the operand must be asserted (on) prior to providing the remote setting
password to gain setting access.
The
Access Authorized Timeout
setting represents the timeout delay remote setting access. It applies when the
Remote
Settings Authorized
setting is programmed to any operand except “On” or “Off.” The state of the FlexLogic operand is
continuously monitored for an off-to-on transition. When this occurs, remote setting access is permitted, and the timer
programmed with the
Access Authorized Timeout
setting value is started. When this timer expires, remote setting access
is denied immediately. If access is permitted and an off-to-on transition of the FlexLogic operand is detected, the timeout
is restarted. The status of this timer updates every five seconds.
5.3.1.3 EnerVista security
Enable the security management system
The EnerVista security system allows an administrator to manage access privileges of multiple users of EnerVista.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...