CHAPTER 8: APPLICATION OF SETTINGS
BIASED CHARACTERISTIC BREAKPOINTS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
8-5
8
•
The trip signal are routed directly to the B-6 and B-7 breakers while it is supervised by the status of S-2, S-4 and S-6 for
the B-2, B-3 and B-4 breakers, respectively
Figure 8-4: South bus zone
8.3 Biased characteristic breakpoints
8.3.1 Description
The limits of linear operation of the CTs need to be found in order to set the breakpoints of the biased differential
characteristic. The settings for the North and South bus relays are analyzed simultaneously from this point on as the two
differential zones share some CTs and the results of computations apply to both the relays.
For microprocessor-based relays it is justified to assume the burden of the CTs to be resistive. The limits of the linear
operation of a CT, neglecting the effects of the DC component and residual magnetism, can be approximated as follows:
Eq. 8-1
where
I
max
is the maximum secondary current transformed without saturation (AC component only, no residual magnetism),
R
s
is the total burden resistance
V
sat
is the saturation voltage of the CT
The total burden resistance depends on both the fault type and connection of the CTs. For single-line-to-ground faults and
CTs connected in Wye, the burden resistance is calculated as:
Eq. 8-2
where
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...