5-212
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-108: Ground IOC1 logic
5.7.7 Breaker failure (ANSI 50BF)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
BREAKER FAILURE
BREAKER FAILURE 1(6)
BREAKER FAILURE 1
BF1 FUNCTION:
Disabled
Range: Disabled, Enabled
BF1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
BF1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4, SRC 5, SRC 6
BF1 USE AMP SUPV:
Yes
Range: Yes, No
BF1 USE SEAL-IN:
Yes
Range: Yes, No
BF1 3-POLE INITIATE:
Off
Range: FlexLogic operand
BF1 BLOCK:
Off
Range: FlexLogic operand
BF1 RETRIP PICKUP
DELAY: 0.033 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 PH AMP SUPV
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 N AMP SUPV
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 USE TIMER 1:
Yes
Range: Yes, No
BF1 TIMER 1 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 USE TIMER 2:
Yes
Range: Yes, No
BF1 TIMER 2 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 USE TIMER 3:
Yes
Range: Yes, No
BF1 TIMER 3 PICKUP
DELAY: 0.000 s
Range: 0.000 to 65.535 s in steps of 0.001
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...