CHAPTER 6: ACTUAL VALUES
STATUS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
6-7
6
stNum
— State number. The most recently received value in GOOSE message field stNum. The publisher increments stNum
each time that the state of one or more of the GOOSE message members is sent with a revised value.
sqNum
— Sequence number. The most recently received value in GOOSE message field sqNum. The publisher sets sqNum
to zero each time the state of one or more of the GOOSE message members is sent with a new value, and it increments it
whenever a GOOSE message is resent without any member value change.
IGMP
— Multicast (SSM and ASM) modes of R-GOOSE reception require that the B30 device subscribe to a multicast group
over the Internet Group Management Protocol (IGMP) enabled network. R-RxGOOSE## IGMP status On indicates that IGMP
negotiation with a network device (for example a router) was successful. In the case where setting R-RxGOOSE1 DST IP is
configured to a multicast address and this status indicates Off, R-GOOSE reception cannot be successful, and therefore
communication network diagnosis needs to be carried out. This status is relevant to R-GOOSE reception when configured
for SSM or ASM reception modes. It is not relevant for GOOSE or for R-GOOSE in unicast reception mode.
6.3.10 Digital counters
ACTUAL VALUES
STATUS
DIGITAL COUNTERS
DIGITAL COUNTERS Counter 1(8)
The present status of the eight digital counters displays here. The status of each counter, with the user-defined counter
name, includes the accumulated and frozen counts (the count units label also appears). Also included, is the date and time
stamp for the frozen count. The
COUNTER 1 MICROS
value refers to the microsecond portion of the time stamp.
6.3.11 Selector switches
ACTUAL VALUES
STATUS
SELECTOR SWITCHES
The display shows both the current position and the full range. The current position only (an integer from 0 through 7) is the
actual value.
6.3.12 Flex States
ACTUAL VALUES
STATUS
FLEX STATES
The B30 is provided with optional IEC 61850 capability. This feature is specified as a software option at the time
of ordering. See the Order Codes section of chapter 2 for details.
DIGITAL COUNTERS
Counter 1
Counter 1 ACCUM:
0
Counter 1 FROZEN:
0
Counter 1 FROZEN:
1970/01/01 00:00:00
Range: YYYY/MM/DD HH:MM:SS
Counter 1 MICROS:
0
Range: 0 to 4294967295 in steps of 1
SELECTOR SWITCHES
SELECTOR SWITCH 1
POSITION: 0/7
Range: Current Position / 7
SELECTOR SWITCH 2
POSITION: 0/7
Range: Current Position / 7
FLEX STATES
PARAM 1: Off
Off
Range: On, Off
PARAM 256: Off
Off
Range: On, Off
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...