CHAPTER 5: SETTINGS
PRODUCT SETUP
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-91
5
XCBR1 BlkCls ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the breaker 1 signal marked
Bkr0XCBR1.BlkCls.ctlVal signal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings > System Setup section
later. This signal when true blocks breaker 1 close control while the operand selected by setting XCBR1 ST.LOC OPERAND
is not active.
CSWI1 Pos ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security, direct-with-enhanced-security, sbo-with-
enhanced-security
Default: direct-with-normal-security
This setting selects the control model clients must use to successfully control the breaker 1 signals marked
BkrCSWI1.PosOpn.ctlVal and BkrCSWI1.PosCls.ctlVal on the Breaker Control Logic (Sheet 1 of 2) diagram in the Settings >
System Setup section earlier. These signals force a breaker 1 three-phase trip or close control while the operand selected
by setting XCBR1 ST.LOC OPERAND is not active.
CSWI1 Pos sboTimeout
Range: 2 to 60 s in steps of 1 s
Default: 30 s
This setting specifies the maximum time between a select and an operate command to breaker 1 via BkrCSWI1.Pos in
order for the operand to be successful. This setting is only relevant when CSWI1 Pos ctlModel is sbo-with-normal-
security or sbo-with-enhanced-security.
CSWI1 Pos operTimeout
Range: 0.000 to 2.000 s in steps of 0.001s
Default: 0.100 s
This setting specifies the maximum time between an operate command to breaker 1 via BkrCSWI1.Pos until
BkrCSWI1.Pos.stVal enters the commanded state. The command terminates if the commanded state is not reached in
the set time.
Switches
The UR disconnect switch control and status monitoring elements have certain settings that configure how the IEC 61850
protocol interacts with these elements. These settings are described in this section. See the Settings > System Setup >
Disconnect Switches section later in this chapter for details on the operation of the disconnect switch control elements.
Navigate to
Settings > Product Setup > Communications > IEC 61850 > System Setup > Switches > Switch 1
to access
the settings that configure the IEC 61850 protocol interface with the first disconnect switch control and status monitoring
element. The settings and functionality for the others are similar.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...