5-256
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
INPUTS/OUTPUTS
CHAPTER 5: SETTINGS
5
I
n
is the measured overload RMS current at index n
E
n
is the accumulated energy at index n
E
n – 1
is the accumulated energy at index n – 1
The thermal overload protection element removes the
THERMAL PROT 1 OP
output operand when E < 0.05. In case of
emergency, the thermal memory and
THERMAL PROT 1 OP
output operand can be reset using
THERM PROT 1 RESET
setting.
All calculations are performed per phase. If the accumulated energy reaches value 1 in any phase, the thermal overload
protection element operates and only resets when energy is less than 0.05 in all three phases.
Table 5-33: Typical time constants
The figure shows the logic for the thermal overload protection element.
Figure 5-138: Thermal overload protection logic
5.9 Inputs/outputs
5.9.1 Contact inputs
SETTINGS
INPUTS/OUTPUTS
CONTACT INPUTS
Protected equipment
Time constant
Minimum reset time
Capacitor bank
10 minutes
30 minutes
Overhead line
10 minutes
20 minutes
Air-core reactor
40 minutes
30 minutes
Busbar
60 minutes
20 minutes
Underground cable
20 to 60 minutes
60 minutes