CHAPTER 5: SETTINGS
CONTROL ELEMENTS
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-235
5
Make the following changes to setting group control in the
SETTINGS
CONTROL ELEMENTS
SETTING GROUPS
menu:
SETTING GROUPS FUNCTION
: “Enabled”
SETTING GROUPS BLK
: “Off”
GROUP 2 ACTIVATE ON
: “SELECTOR 1 POS 2"
GROUP 3 ACTIVATE ON
: “SELECTOR 1 POS 3"
GROUP 4 ACTIVATE ON
: “SELECTOR 1 POS 4"
GROUP 5 ACTIVATE ON
: “Off”
GROUP 6 ACTIVATE ON
: “Off”
Make the following changes to selector switch element in the
SETTINGS
CONTROL ELEMENTS
SELECTOR SWITCH
SELECTOR SWITCH 1
menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:
SELECTOR 1 FUNCTION
: “Enabled”
SELECTOR 1 FULL-RANGE
: “4”
SELECTOR 1 STEP-UP MODE
: “Time-out”
SELECTOR 1 TIME-OUT
: “5.0 s”
SELECTOR 1 STEP-UP
: “PUSHBUTTON 1 ON”
SELECTOR 1 ACK
: “Off”
SELECTOR 1 3BIT A0
: “CONT IP 1 ON”
SELECTOR 1 3BIT A1
: “CONT IP 2 ON”
SELECTOR 1 3BIT A2
: “CONT IP 3 ON”
SELECTOR 1 3BIT MODE
: “Time-out”
SELECTOR 1 3BIT ACK
: “Off”
SELECTOR 1 POWER-UP MODE
: “Synchronize”
Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the following
changes in the
SETTINGS
INPUTS/OUTPUTS
CONTACT OUTPUTS
menu:
OUTPUT H1 OPERATE
: “SELECTOR 1 BIT 0"
OUTPUT H2 OPERATE
: “SELECTOR 1 BIT 1"
OUTPUT H3 OPERATE
: “SELECTOR 1 BIT 2"
Finally, assign configure user-programmable pushbutton 1 by making the following changes in the
SETTINGS
PRODUCT
SETUP
USER-PROGRAMMABLE PUSHBUTTONS
USER PUSHBUTTON 1
menu:
PUSHBUTTON 1 FUNCTION
: “Self-reset”
PUSHBUTTON 1 DROP-OUT TIME
: “0.10 s”
The figure shows the logic for the selector switch.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...