5-60
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
CHAPTER 5: SETTINGS
5
Prefix for GGIO2
Range: 0 to 11 VisibleString characters
Default:
This setting sets the LN Prefix of the Virtual Inputs Interface logical node GGIO2 that is described in the GGIO2 section
later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first character must
be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO2 prefix that is used by the
product.
Prefix for GGIO4
Range: 0 to 11 VisibleString characters
Default:
This setting sets the LN Prefix of the FlexAnalog operand interface logical node GGIO4 that is described in the GGIO4
section later. Valid characters are upper and lowercase letters, digits, and the underscore (_) character. The first
character must be a letter. UR Setup software does not allow entry of a prefix that duplicates any other GGIO4 prefix
that is used by the product.
LLN0.Mod.ctlModel
Range: status-only, direct-with-normal-security, sbo-with-normal-security
Default: sbo-with-normal-security
This setting specifies the control service that clients must use to control the TEST MODE FUNCTION of the B30. An "on"
control to <LDName>/LLN0.Mod changes TEST MODE FUNCTION to Disabled, an "on-blocked" control changes it to
Forcible, and a "test/blocked" changes it to Isolated.
Configuration Type
Range: G2, E3-2.0
Default: G2
This setting is read only. It specifies the method used to describe GOOSE subscription configuration in SCL. See the UR
Family Communications Guide for details. In the G2 mode, the CID file contains IED elements for IEDs subscribed to by
this IED containing GOOSE subscription information. In the E3 2.0 mode, the CID file has only one IED element and
GOOSE subscription information is coded in data objects in the standard LGOS logical node used to monitor reception of
the subscribed GOOSE. UR 7.30 or later accepts either mode. The set value is for the entire EnerVista installation and is
preserved between sessions. To change this global field, click
File > Preferences
and access the IEC 61850 panel; you do
not need to be connected to the device.
Logical devices
The Logical Devices panel contains IEC 61850 settings relevant to the configurable logical devices feature, wherein logical
device naming can be reconfigured and logical nodes re-assigned.
The path is
Settings > Product Setup > Communications > IEC 61850 > Logical Devices
.
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...