6-8
B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
STATUS
CHAPTER 6: ACTUAL VALUES
6
There are 256 FlexState
TM
bits available. The second line value indicates the state of the given FlexState bit.
6.3.13 Ethernet
ACTUAL VALUES
STATUS
ETHERNET
These values indicate the status of the first, second, and third Ethernet links.
6.3.14 Real time clock synchronizing
ACTUAL VALUES
STATUS
REAL TIME CLOCK SYNCHRONIZING
RTC SYNC SOURCE
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
GRANDMASTER ID
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
ACCURACY
is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
PORT 1…3 PTP STATE
is the present state of the port’s PTP clock. The PTP clock state is:
•
Disabled
is the port’s function setting is Disabled
•
No Signal
if enabled but no signal from an active master has been found and selected
•
Calibrating
if an active master has been selected but lock is not at present established
•
Synch’d (No Pdelay)
if the port is synchronized, but the peer delay mechanism is non-operational
•
Synchronized
if synchronized
ETHERNET
ETHERNET PRI LINK
STATUS: Fail
Range: Fail, OK
ETHERNET SEC LINK
STATUS: Fail
Range: Fail, OK
ETHERNET TER LINK
STATUS: Fail
Range: Fail, OK
REAL TIME CLOCK
SYNCHRONIZING
RTC SYNC SOURCE:
None
Range: see below
GRANDMASTER ID:
0X0000000000000000
Range: any 8 octet value
ACCURACY:
999999999 ns
Range: 0 to 999,999,999 ns
PORT 1 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 2 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PORT 3 PTP STATE:
No Signal
Range: Disabled, No Signal, Calibrating, Synch’d (No
Pdelay), Synchronized
PTP - IRIG-B DELTA:
500000000 ns
Range: -500,000,000 to +500,000,000 ns
Summary of Contents for b30
Page 10: ...x B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Page 486: ...5 278 B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Page 616: ...iv B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Page 632: ...xvi B30 BUS DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...